normal operation

without utility power
1c to 1f indicating the remaining
autonomy percentage (< 100,
75, 50, 25%): here < 50%
1g flashing
1 beep every 10 s
your devices are powered by the battery
with utility power
1c to 1f indicating the recharge
percentage of the battery
(100, 75, 50, 25%):
here between 50 and 75%
1f on
silence
your devices are powered by the utility
power
c the "fader" and "booster" functions are
used to keep the output voltage range
(Umax-Umin) compatible with the supply
operating range of your application;
c this operating range can be configured via
the "ESV Driver" software (included in your
CD-ROM);
c on operation in the "fader" or "booster"
range, the indicator light 1d comes flashing.
30
input voltage
variation range
(*)
264 Volts
maxi
rated
184 Volts
mini
(*)
(*) outside the min.-max. range indicated, Pulsar runs in battery backup
(**) standard setting
Pulsar ESV+: 51032616XT/AC
output voltage
variation range
"fader" mode
in operation
248V
204V
"booster" mode
in operation
MGE UPS SYSTEMS
maxi
(**)
rated
mini (**)