Installation Precautions

Installation location

50 mm
1 to
1.5 m
Floor

Remote control wiring

Wiring diagram

Indoor unit
R1
R2
RC wiring (fi eld supply)
• No polarity
Terminals for RC wiring
Attention
 Use the fi eld supplied RC wiring with at least 1 mm in thickness of insulation part including the
sheath.
Wiring Regulations may diff er depending on location. For fi eld wiring rules, please refer to your
LOCAL ELECTRICAL CODES.
You must ensure that installation complies with relevant rules and regulations.
 Be careful not to connect cables to other terminals of indoor units (e.g. power source wiring terminal).
Malfunction may occur.
 Do not bundle together with the power source wiring or store in the same metal tube. Operation error
may occur.
 If noise is induced to the unit power supply, attach a noise fi lter.
Wiring as shown below is prohibited.
Indoor unit
R1 R2
1 2
6
 Install at the height of 1 to 1.5 m from the fl oor
(Location where average room temperature can be
50 mm
detected).
 Keep a space around the remote controller as detailed
on the fi gure shown left.
50 mm
 Avoid the following locations for installation.
• In the shadow or backside of objects deviated from the
room airfl ow
• Location where condensation occurs (The remote
controller is not moisture proof or drip proof)
• Location near heat source
50 mm
 Keep distance of 1 m or more from the TV, radio and
PC. (Image blur or related noise may occur)
 Do not use in special environments.
Use in places with much oil (including machine oil),
steam, fl ammable or corrosive gas, voltage fl uctuation,
surrounding the metal body, may lead to severe
decrease in functionality and damage to parts.
1
2
Indoor unit
R1 R2
RC wiring
RC
 Type of wiring
 Use cables of 0.75 to 1.25 mm
RC
 Total wire length: 100 m or less
 Number of connectable units
 Remote controller:
1 unit connection only
 Indoor unit: Max. 8
.
2