After an additional time delay of approximately 12
minutes, the unit will go into Standby mode.
The filter cleaning delay is set by the DIR_time relay,
and the stop delay is set by the SSR_time relay.
• With all valves at the workstations closed, check
that the motor slows down (a distinct change in
sound can be heard), and that switching to Idling
mode with filter cleaning takes place after approx-
imately 10 seconds.
Approximately 12 minutes after the unit has switched
to Idling mode, it should go to Standby mode due to
the SSR function switching off.
5.3 Start the unit
For more information regarding initial start-up, see
the 'Installation and service manual'.
Start the unit as follows:
1
Turn the maintenance switch to position 1.
2
Compressed air connected to the unit
3
Press the Standby/Running button on the control
panel, see
Figure 5
item 9. The white lamp lights
up and the display shows 'Standby'.
4 The unit starts when the test start button is
pressed,
Figure 5
item 8, or when a valve is
opened at a workstation.
Always switch off the unit at the end of the shift
by pressing the Standby/Running button on the
control panel, or use the weekly timer, see
tion 7.2.3 Weekly
timer.
5.4 Unit operation modes
FlexPAK 800/1000 DX has the following four opera-
tion modes:
1
Off mode
2
Standby mode
3
Running mode
4 Idling mode
See
Section 6.1 Status messages
about each mode.
How the unit moves from one operation mode to an-
other is explained below. See also
chart showing how the unit goes through its four dif-
ferent operation modes.
6 PLC messages
The following sections show the different status, warning and alarm messages that can be seen in the PLC dis-
play. See also the PLC Settings Manual and the Installation and Service Manual.
If a message is displayed that is not shown in this user manual, see the PLC Settings Manual for more in-
formation.
If a warning or alarm is displayed that is not shown in this user manual, see the PLC Settings Manual for
more information and contact a Nederman authorized service technician.
FlexPAK 800/1000 DX
As discussed in
unit is in Off mode, the unit can be put into Standby
mode with its motor off and the Filter Cleaning Valve
(FCV) closed by pressing the Standby/Running but-
ton. While the unit is in Standby mode, the unit can be
put back into Off mode again by pressing the Standby/
Running button.
The unit goes from Standby mode into Running
mode when it receives a pilot signal by a valve being
opened at one or more work stations (in other words,
someone starts to work). The unit's motor is now on
and the FCV is closed. The DIR_Time and SSR_Time
timers are not started, see
Section 7.2.1 SSR_Time
The unit stays in Running mode as long as there is an
active pilot signal. However, the unit can still be put
into Off mode by pressing the Standby/Running but-
ton.
Note that if only one workstation is connected to the
unit, or if only one work station is in use and work
stops at that one station, the pilot signal stops. If
there is more than one work station connected to the
unit, and more than one work station is in use, the pi-
lot signal only stops if work stops at all workstations
(in other words, all valves close).
When the pilot signal stops, the DIR and SSR timers
start. If work resumes at one or more work stations
within 10 seconds, the unit stays in Running mode.
The DIR and SSR timers are reset back to zero and are
Sec-
stopped.
If DIR_Time is set for 10 seconds (default), and the
pause in work is longer than 10 seconds, DIR_Time
elapses. The unit then goes into Idling mode with its
motor on and the FCV open.
If a new pilot signal is sent within 12 minutes, the unit
goes back into Running mode. The DIR and SSR timers
are again reset to zero and are stopped. However,
if SSR_Time is set for 12 minutes, which is the de-
fault setting, and there is no new pilot signal within 12
minutes, SSR_Time also elapses.
for more information
The unit then goes into Standby mode until it either
receives a new pilot signal that puts the unit back
into Running mode, or the unit is turned off (in oth-
Figure 18
for a flow
er words, put into Off mode) by the weekly timer,
see
Standby/Running button.
Section 5.3 Start the
Section 7.2.2 DIR_Time
'Section 7.2.3 Weekly timer
unit, when the
and
or by pressing the
27