Degree of effect
Setting range: 1 – 10
This function can only be used if your electricity supplier
supports Smart price adaption, if you have an hourly
tariff agreement and an active myUplink account.
Smart price adaption™ moves the heat pump's consump-
tion over 24 hours to periods with the cheapest electri-
city tariff, which gives savings for hourly rate based
electricity contracts. The function is based on hourly
rates for the next 24 hours being retrieved via myUplink
and therefore an internet connection and an account for
myUplink are required.
You can choose which parts of the installation are to be
S
affected by the electricity price and to what extent; the
higher value you select, the greater the effect the elec-
tricity price has.
NOTE
A value that is set high may result in increased
savings, but may also affect the comfort.
MENU 7.1.7 - COOLING
This menu contains sub-menus where you can make
advanced settings for cooling operation.
MENU 7.1.10.2 - AUTO MODE SETTINGS
Start cooling
Setting range, cooling, 4-pipe: 15 – 40°C
Auto: When the operating mode is set to "Auto", the in-
stallation selects when start and stop of additional heat
and cooling/heat production are permitted, depending
on the average outdoor temperature.
Filtering time: You can set the time over which the aver-
age outdoor temperature is calculated. If you select 0,
the current outdoor temperature is used.
Used as cooling/heating sensor
Here you select the sensor that will be used for cool-
ing/heating. If BT74 is installed, it will be preselected
and no other option is possible.
Set point value cool/heat sensor: Here, you can set the
indoor temperature at which the installation will change
between heating and cooling operation.
Heating at subnormal room temp: Here, you can set
how much the room temperature can drop below the
desired temperature before the installation switches to
heating operation.
Cooling at excess room temp: Here, you can set how
much the room temperature can increase above the
desired temperature before the installation switches to
cooling operation.
26
MENU 7.1.10.3 - DEGREE MINUTE SETTINGS
Cooling, auto
Setting option: on/off
Start active cooling
Setting alternative: 10 – 300 DM
DM = degree minutes
Degree minutes are a measurement of the current
heating requirement in the house and determine when
the compressor respectively additional heat will
start/stop.
Start active cooling: Here, you set when active cooling
will start.
MENU 7.2.18 - COOLING, 4 PIPE (ACS)
Operating mode EQ1-GP12
Setting range: Auto, Intermittent
Speed EQ1-GP12
Setting range: 1 - 100%
Pump
Setting range: Wilo Yonos Para, Xylem Lowara E6
Operating mode EQ1-GP12
Auto: GP12 runs according to the current operating
mode for the compatible product.
Intermittent: GP12 starts approx. 20 seconds before,
and stops approx. 20 seconds after, the compressor.
Speed EQ1-GP12
Here, you set the speed of GP12.
Pump
Here, you set which pump is installed in the system.
MENU 7.5.3 - FORCED CONTROL
Here you can force control the various components in
the installation. The most important safety functions
remain active however.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
Caution
Also see the Installer manual for the indoor
module.