REVERSING VALVE, COOLING (EQ1-GN12)
Install the reversing valve (QN12) with port AB as the
incoming supply line from the heat pump, port A to the
volume vessel and port B to the heating system. Install
it so that port AB is open towards port B when the motor
is in standby. On a signal, port AB opens towards port
A.
S
B
AB
TEMPERATURE SENSOR, COOLING
(EQ1-BT64)
Place the cooling sensor (EQ1-BT64) on the lower part
of the volume vessel, cooling (CP10.2), on the supply
line from the volume vessel, see
with ACS
310".
NOTE
Sensor and communication cables must not
be laid near power cables.