Installation space

Reserve sufficient space required for installation or service work.
250 or more
Installing indoor unit on high ceiling
Set the installable height of the ceiling within 4 m, otherwise the air distribution will become poor.
If height of ceiling exceeds 3.5 m, hot air becomes difficult to reach the floor surface, and then the change of setup
of high ceiling is necessary.
For the change method of high ceiling, refer to the application control, "Installing indoor unit on high ceiling" in this
Manual.
List of installable ceiling height
SET DATA
0000
Standard (Factory default)
0001
High ceiling 1
The lighting time of the filter sign (notification of filter cleaning) on the remote controller can be changed according
to installation conditions.
When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room,
the detection temperature of heating can be raised.
For change the setup time, refer to the application control, "Filter sign setting" and "To secure better effect of
heating" in this Manual.
Wireless type
Decide the position which remote controller is operated and the installation place.
And then refer to the Installation Manual of the wireless remote controller kit sold separately.
(The signal of the wireless type remote controller can be received within approx. 8 m. This distance is a criterion
and varies a little according to capacity of the battery, etc.)
• To prevent malfunction, select a place where is not affected by a fluorescent lamp or direct sunlight.
• Two or more (up to 6 units) wireless-type indoor units can be set in a room.
59-EN
(Unit: mm)
250 or more
3.5 m or less
4.0 m or less
4

Installation

CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to
use buffering cloth, etc. to not damage the unit.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.

External dimensions

Upper pipe draw-out port (Knockout hole)
Power supply wire take-in port (Knockout)
128
Remote controller wire take-in port
(Knockout hole)
84
Refrigerant pipe
Left drain size
(Liquid side ØC)
B (Hanging position)
Refrigerant pipe (Gas side ØD)
Hanging bolt
Ceiling surface
Unit
A
– 30 –
210
Pipe draw-out port (Knockout hole)
216
167
Drain port VP20
110
76
105
(Inner dia. Ø26, hose attached)
Drain pipe
75
97
connecting port
146
Remote controller wire take-in port
Power supply wire take-in port (Knockout hole)
347
Remote controller wire take-in port
262
(Knockout hole)
135
Outside air take-in port (Knockout hole Ø92)
Pipe hole on wall (Ø100 hole)
Drain left pipe draw-out port
(Knockout hole)
Model MMC-
A
Wireless sensor
AP015 type, AP018 type 910
mounting section
AP024 type, AP027 type 1180 1125
AP036 type, AP048 type 1595 1540
(Unit: mm)
84
B
C
D
855
Ø6.4 Ø12.7
Ø9.5 Ø15.9
60-EN