 Installation under high-humidity atmosphere
In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere
(dew-point temperature: 23 °C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the fresh air
4. Installation to a kitchen
• In the above cases, additionally attach the heat insulator to all positions of the air conditioner, which come to
contact with the high-humidity atmosphere. In this case, arrange the side plate (Check port) so that it is easily
removed.
• Apply also a sufficient heat insulation to the duct and connecting part of the duct.
[Reference]
Condensation test conditions
27 °C dry bulb temperature
Indoor side:
24 °C wet bulb temperature
Air volume:
Low air volume, operation time 4 hours
 Installation space
Reserve sufficient space required for installation or service work.
Air discharge
100 or more
<Under air intake>
5 or more
210
Air intake
Ceiling
50 or more
2500 or more
Floor surface
95-EN
5 or more
235 or more
210
250 or
more
<Back air intake>
235 or
Air intake
more
Ceiling
300 or more
Floor surface
 Service space
50
Ceiling
(Unit: mm)
5 or more
235 or
210
more
2500 or more
– 48 –
Air discharge
50
945
Service door (Ceiling opening)
645
945
Service door (Ceiling opening)
745
945
(Unit: mm)
645
645
Air filter
745