CIAT LN Serie Montage-, Betriebs- Und Wartungsanweisung Seite 27

Kaltwassertz mit luftgekühltem verflüssiger
Inhaltsverzeichnis

Werbung

Analyse,
principaux
remèdes dépannage
Anomalies
Anomalies
6 - Défaut moteur
6 - Motor fault
7 - Température de sortie fluide froid
trop élevée
7 - Chilled fluid outlet temperature too
high
high
Analysis,
main repair
remedies
Causes probables
Possible causes
S
S Motor starts too close, anti short cycling out of order
S
S
S Thermic faulty or out of order
S
S
S Supply voltage too low
S
S
S Motor not cooled sufficiently
S
S
S Faulty operation of intensity limiting device
S
a) Avec pression d'aspiration supérieure à la normale
a) With intake pressure higher than normal
a) Bei erhöhtem Ansaugdruck
S
S Regulating device setting point out of order
S
S
S Thermal load higher than the one forecasted
S
S
S Water flow too high
S
S
S Electronic control not working
S
S
S Chilled fluid inlet or condenser air temperature too high, the intensity
limiting device prohibits capacity increase.
S
S
S Capacity variation assemblies faulty
S
b) Avec pression d'aspiration inférieure à la normale
b) With intake pressure lower than normal
b) Bei zu niedrigem Ansaugdruck
S
S Lack of refrigerant fluid
S
S
S Faulty refrigerant fluid supply to the evaporator
S
27
Analyse,
Störungsbehebung
Instructions
Instructions
S
S Set the correct delay between two starts
S
S
S Set or replace
S
S
S Check the electrical installation and contact, if required, the power
supplying company
S
S
S Check that nothing impedes motor cooling
S
S
S Check the operation of capacity control relay driven by the limiting
device. Check and adjust, if necessary, the setting of the limiting
device.
S
S
S Display the correct setting
S
S
S Check the balances (or put on additional unit on line if available)
S
S
S Adjust the flow according to forecasted value
S
S
S Check operation of temperature and capacity controlers
S
S
S Proceed as under 2 for the condenser
For the evaporator side : wait if the load is normal, the temperature will
decrease progressively
S
S
S Check the capacity variation coils as well as the absence of leak on
the assembly
S
S
S Locate the leak(s) and top up the load
S
S
S Check the electrical and expansion valves and possibly the filter
dryer fouling.