00: Exit settings
Interface

3-6. Operating Mode Description

Operating mode
Online mode
ECO mode
Frequency
Converter mode
Battery mode
Bypass mode
Standby mode
Fault mode
Setting
Exit the setting mode.
Description
When the input voltage is within acceptable
range, the UPS will provide pure and stable AC
power to output. The UPS will also charge the
battery at online mode.
Energy saving mode:
When the input voltage is within voltage
regulation range, the UPS will bypass voltage to
output for energy saving. The UPS will also
charge the battery in ECO mode.
When input frequency is within 40 Hz to 70 Hz,
the UPS can be set at a constant output
frequency, 50 Hz or 60 Hz. The UPS will continue
to charge battery under this mode.
When the input voltage is beyond the acceptable
range or there's a power failure, the UPS will
provide power from battery and a warning alarm
will sound every 5 seconds.
When the input voltage is within acceptable
range, but UPS is overload, the UPS will enter
bypass mode or can be set from the front panel.
An alarm will sound every 10 seconds.
The UPS is powered off and will not output
power, but charges batteries.
When a fault has occurred, the ERROR icon and
the fault code will be displayed.