Herunterladen Inhalt Inhalt Diese Seite drucken

Online USV XANTO RT 1000 Benutzerhandbuch Seite 80

Rt-serie
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

OUTPUT
Rated voltage (V)
Waveform
Frequency, UPS operation
Distortion factor,
linear load
Distortion factor,
non-linear load
Crest factor
Power factor
Overload behaviour
Normal mode, inverter
overload <105%
Normal mode, inverter
overload 105 - 125%
Normal mode, inverter
overload >125%
Battery mode, inverter
overload <105%
Battery mode, inverter
overload 105 - 125%
Battery mode, inverter
overload >125%
Efficiency, normal mode
Efficiency, battery mode
Output socket
BATTERY
Type
Quantity
Service life
Charging time
Charging current (A)
Battery test
220V (standard), 230V/240V configurable
Sinusoidal
50Hz +/- 0.2%
< 2% THD, R load
< 5% THD, RCD load
typ. 0.7 (0.65 – 1.0)
Has no effect
5 minutes, then bypass mode
1 minute, then bypass mode
Has no effect
30 seconds, then standby mode
250ms, then standby mode
4x
IEC320 C13
IEC320 C13
CSB GP 1272
CSB GP1272
F2
12V/7.2Ah
12V/7.2Ah
3
3-5 years in accordance with EUROBAT
5 hours to reach 90% capacity
Automatic, manual, remote
Seite 80 von 128
3:1
>88%
>83%
2x
4x
IEC320 C13
+ terminal
CSB HR
F2
1234W F2
12V/9Ah
6
6
1

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Xato rt 2000Xanto rt 3000Rt1000Rt3000Rt2000

Inhaltsverzeichnis