Commissioning
5.2 Changing the Polarity-Reversal Frequency
Check the test values for the injection unit 7XT71 on the 7UM62/7UM85.
²
If the test values are correct, setting the frequency is completed.
²
Note the new frequency on the label on the device.
²
[scaufklfrq, 1, en_US]
Figure 5-4
NOTE
i
i
If the 7UM62/7UM85 does not display correct values, repeat the frequency setting on the injection unit
7XT71 until the values roughly correspond to the required operating conditions.
34
Label for the Set Frequency
SIPROTEC 4/5, Injection unit 7XT71, Manual
C53000-B1174-C128-8, Edition 05.2020