Authorized Service immediately.
The earthed outlet must be in close
vicinity of the appliance. Never use an
extension cord.
The supply cable should not contact the
product's hot surface.
In case of any damage to the supply
cable, make sure to call the Authorized
Service. The cable must be replaced by
the Authorized Service.
Wiring of the appliance must be
performed by the Authorized Service.
H05VV-F type supply cable must be
used.
Faulty
wiring
appliance. Such a damage will not be
covered under the warranty.
The appliance is designed to connect
to 220-240V~ electricty is different
than the value given above, call the
Authorized Service immediately.
The Manucaturer Firm declares that its
bears no responsibility whatsover for
any kind of damage and loss arising
from not complying with safety norms!
WIRING AND SAFETY OF THE
BUILT-IN COMBINED OVEN
Wiring of the appliance must be
performed by the Authorized Service.
The appliance is designed to connect
to 220-240V~ and 380-415V 3N ~
electricity. If the mains electricity is
different than the value given above,
call the Authorized Service immediately.
Connection
of the appliance must be as shown in
Figure 6. The appliance is designed for
fixed connection to the mains. There
is to install an all pole disconnector
inside they supply circuit with a contact
may
damage
openning of at least 3mm ( rated 40A,
delay functioning type ).
3x2.5mm 220V~
3x2.5mm 230V~
3x2.5mm 240V~
For models over 9500W, wires with a diameter of
3x4.0 mm must be used.
2
the
EN -11-
5x1.5mm 380V~, 3N~
2
5x1.5mm 400V~, 3N~
2
5x1.5mm 415V~, 3N~
2
2
2
2
Figure 6