2. Non-incendive wiring (FM US only)
SITRANS Probe LU
7ML1234-78910-ABC-D
Serial No: GYZ / S1034567
Power Rating: 24V
FM Class 1, Div 2 connection drawing
number 23650583 can be downloaded from the product page of our website at:
www.siemens.com/probelu. Go to Support > Installation Drawings > Level Measurement >
Continuous - Ultrasonic.
• For power demands, see
The following instructions apply to the SITRANS Probe LU covered by certificate number SIRA
06ATEX2355X:
1. For use and assembly, refer to the main instructions.
2. The equipment is certified for use as Category 1G equipment.
3. The equipment may be used with flammable gases and vapors with apparatus groups IIA,
4. The equipment is certified for use in an ambient temperature range of –40 C to +80 C.
5. The equipment has not been assessed as a safety related device (as referred to by
6. Installation and inspection of this equipment shall be carried out by suitably trained
7. Repair of this equipment shall be carried out by suitably trained personnel in accordance
8. Components to be incorporated into or used as replacements in the equipment shall be
9. It is the responsibility of the user to ensure that manual override is possible in order to
10. The 'X' suffix to the certificate number relates to the following special conditions for safe
A5E32168031
Downloaded from
www.Manualslib.com
Encl.:
NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Nom., 30V
Max., 4-20 mA
Siemens Milltronics Process Instruments, Peterborough
Assembled in Canada with domestic and imported parts
Loop Voltage versus Loop Resistance
Instructions specific to hazardous area installations
(Reference European ATEXDirective 94/9/EC, Annex II, 1/0/6)
IIB, and IIC, and temperature classes T1, T2, T3, and T4.
Directive 94/9/EC Annex II, clause 1.5).
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-
17 in Europe).
with the applicable code of practice (e.g. EN 60079-19 within Europe).
fitted by suitably trained personnel in accordance with the manufacturer's
documentation.
shut down the equipment and protective systems incorporated within automatic
processes which deviate from the intended operating conditions, provided that this does
not compromise safety.
use:
Parts of the enclosure may be non-conducting and may generate an ignition-
capable level of electrostatic charge under certain extreme conditions. The
user should ensure that the equipment is not installed in a location where it
may be subjected to external conditions (such as high-pressure steam) which
might cause a build-up of electrostatic charge on non-conducting surfaces.
SITRANS Probe LU (HART) – QUICK START MANUAL
manuals search engine
Class I,Div.2,
Group A,B,C,D
Temp.Code:T5
HART
on page 4 of Appendix A.
(continued on next page)
Page EN-7