3-2. How to Fix Installation Plate

The mounting wall is strong and solid enough to prevent it from
vibration.
Bolt-
size
Wall
More than 551
M8
Appropriate
6
Plugs (M8)
Wall
Washer
Installation
plate a
≥1550 from
ground
71
The centre of installation plate should be at more than 551 mm
at right and left of the wall.
The distance from installation plate edge to ground should more
than 1550 mm.
A lways mount the installation plate horizontally by aligning
the marking thread and using a level gauge.
M ount the installation plate on the wall with 6 sets of plug,
bolt and washer (all non-supply) with size M8.
CAUTION
Also avoid areas where electrical wiring or conduits are
located.
The above precautions are also applicable if tubing goes
through the wall in any other location.
(1) Using a sabre saw, keyhole saw or hole-cutting drill
attachment, cut a hole in the wall.
Indoor side
NOT E
Hole should be made at a slight downward slant to the outdoor
side.
Hole Dia. (mm)

3-3. To Drill a Hole in the Wall and Install a Piping

Sleeve

(1) Insert the piping sleeve to the hole.
(2) Fix the bushing to the sleeve.
(3) Cut the sleeve until it extrudes about 15 mm from the wall.
CAUTION
When the wall is hollow, please be sure to use the Piping
sleeve assembly to prevent dangers caused by mice biting the
connection cable.
(Unit: mm)
Wall
More than 551
Bolt-size M8
6
Installation
plate c
160
200
Outdoor side
70
(4) Finish by sealing the sleeve with putty or caulking
compound at the final stage.
Indoor
Indoor
unit
body
Sleeve for tube
assembly
745
ø70 mm
through hole

3-4. Indoor Unit Installation

1. E ngage the slots on the
indoor unit to the hooks of
installation plate
the hooks are properly
seated on the installation
plate by moving it left and
right.
2. F ix the screws
holes on the hooks of
installation plate
illustrated at right.

3-5. Water Piping Installation

T he minimum requirement of water in the system is 50 litres.
If this value could not be achieved, please install additional
buffer tank (field supply).
W ater inlet and water outlet in indoor unit are used for
connection to water circuit.
P lease request a licensed technician to install this water
circuit.
T his water circuit must comply with all relevant European and
national regulations, i.e. IEC/EN 61770.
B e careful not to deform the piping with excessive force when
doing piping connection job.
U se Rp 1-1/4" nut for both water inlet and outlet connection
and clean all pipings with tap water before connecting to the
indoor unit.
C over the piping end to prevent dirt and dust when inserting it
through a wall.
C hoose proper sealer which can withstand the pressures and
temperatures of the system.
I f an existing tank is to be connected to this indoor/outdoor
unit, ensure the pipings are clean before water piping
installation is carried out.
A n external filter (30 mesh or more, field supplied) must
be installed before the water inlet of the indoor unit (with
"WATER IN" indication).
W ater operating temperatures (Minimum ~ Maximum) : 5 °C
~ 65 °C
W ater operating pressures (Minimum ~ Maximum) : 0.05 MPa
~ 0.3 MPa
9
Wall
Outdoor
15 mm
Approx. 5 ~ 7 mm
Bushing for tube
Assembly
Putty or caulking compound
Slots
Installation
plate a
. Ensure
a
Indoor unit (back)
to the
b
, as
c
Hooks
Wall
Installation
plate c
Screws b

Werbung