Device
Sub-
Device
ID
ID
0x01
0x00
VR660
0x02
0x00
A200R
0x03
0x01
CAM
0x04
0x00
APLUS
0x05
0x00
V604s
0x05
0x01
VB604s
0x05
0x02
VC604s
0x05
0x03
VQ604s
0x07
0x00
VS30
Temperature transmitter
0x08
0x00
DM5S
Multi transmitter standard
0x08
0x01
DM5F
Multi transmitter fast
0x08
0x02
DM5E
Multi transmitter energy
0x08
0x03
DM5SC
Multi transmitter monitoring
0x09
0x00
CAM Quality
System analysis ___________________
0x0A
0xFF
HW730
Transmitters for angular position
0x0B
0xFF
CAM Profinet CAM Ethernet Buscard with Profinet
6.3 Process image
Definition of all volatile and non-volatile parameters and
variables.
6.4 Measured values
The measured angle is available in two different formats.
Adress
Length
Designation
40001
2
PHI_FLOAT
40003
1
PHI_INT

6.5 General information

Adresse
Length Designation
40101
1
FW_REVISION UINT16
40102
1
FW_VERSION
40103
1
MB_VERSION
40104
1
RESERVE
40105
2
SERIAL
6.6 Configuration
Adresse
Length
Designation
40201
1
CONFIG
18
Description
Temperature controller
Display
Universal measuring unit for heavy current
variables
Multifunctional display
Universal transmitter
Universal transmitter multi in/out
Universal transmitter second Relay
Universal transmitter fast setting time
Typ
Description
FLOAT
Measured value in degrees
(0.0° ≤ PHI_FLOAT < 360.0°)
UINT16
The value for the 360°
angle can be configured via
NO_STEPS.
(0 ≤ PHI_INT < NO_STEPS)
Typ
Description
Revisions number
UINT16
Firmware version
Byte 1
Byte 0
v 1.00
1.00: Version number
Hexadecimal representation of
the version number
UINT16
Version of the Modbus image.
UINT16
Reserved
UINT32
Serial number of the device
Typ
Description
UINT16
Bit 0: Sense of rotation
0
clockwise
1
counterclockwise
Bit 2 ... 15: Reserved
Bit 8 ... 15: Reserved
Operating Instructions HW730 Be
40202
1
NO_STEPS
40203
2
ZERO
NO_STEPS refers to the subdivision of the entire measuring
range of 0...360 into number of steps.
(E.g. NO_STEPS 100 means to divide 0...360 into 100 parts
of 3.6°)
Adress
Length
Designation
10001
1
SET_ZERO
6.7 Network configuration IPv4
Adress
Length
Designation
40301
2
IPv4
40303
2
SUBNETv4
40305
2
GATEWAYv4
6.11 TCP-Port für Modbus/TCP
Port 502 is always used for Modbus/TCP as a standard.
HW730-ETH is always accessible via this port. Further con-
nections can be alternatively realised via the following con-
figured port.
Adresse
Length
Designation
40315
1
TCP_PORT
6.12 Name of device
A name may be allocated to each device. This simplifies the
identification of the device via the search service.
Adresse
Length
Designation
40401
16
NAME
7. Mounting
See page 23.

8. Electrical connections

For connecting the external wires, the transmitter has a
plug connector M12x1 / 4 poles d-coded or a cable glands
M16x1.5. During the version with a cable glands the con-
nection via a spring-type terminal block made in accordance
with diagram of connections.
Permissible cable:
Cable length:
Connection allocation plug M12/4-pole d-coded
1
2
4
3
Number of steps per 360°
UINT16
Default: 4096
Zero point
FLOAT
Default: 0.0
Typ
Description
Determine current angle to be
COIL
the zero point
Typ
Description
UINT32
IP-Adress
UINT32
Subnetmaske
UINT32
Standard-Gateway
Typ
Description
UINT16
Alternative Modbus/TCP port
Typ
Description
Identification of the device
in text form
CHAR[32]
Allowed characters:
'A'...'Z', 'a'...'z', '_',
0-terminated
Ethernet CAT5
100m
Pin
Signal
1
Rx+
2
Tx+
3
Rx-
4
Tx-