Pointek CLS200/300 Digital unit on a PROFIBUS
network
Wiring: connection to a PROFIBUS PA network
WARNING: The requirements listed under WARNINGS on page 5 must be fulfilled.
Notes:
• Lay PA cable separately from power cable with voltages greater than 60 V AC.
• Avoid locating Pointek CLS200/300 near large electrical equipment wherever possible.
• Connect the cable shield to earth (for example, to the housing by means of a metallic
screwed gland).
PROFIBUS PA connection to screw terminals
Connect the PROFIBUS cable to the screw terminals, following the instructions on page 6.
PROFIBUS PA connection via M12 plug
If an M12 plug is installed on thePointek
CLS200/300 enclosure, a female M12 receptacle
is required on the end of the cable, to complete
the bus connection to PROFIBUS PA.
The usual PROFIBUS PA recommendation is to
ground the shield on both the device side and
the cable side. In some cases (for example, on
cathodically protected tanks), it may be
preferable to ground one side only, to avoid
ground loops.
Follow the instructions
accompanying the
female receptacle.
Page EN-10
Downloaded from
www.Manualslib.com
.
4
Front view of pin
insert and pins
1
PIN PROFIBUS PA
1
PA+
2
not connected
3
PA–
4
shield, connected to ground
Pin assignment: device side
Pointek CLS200/300 (Digital) – QUICK START MANUAL
manuals search engine
thread M12 x 1
3
2
positioning lug
Pin assignment: cable side
lid with window
digital display
M12 plug
(device side)
M12 receptacle
(cable side)
4
3
Front view of
sleeve insert and
2
1
sleeves
positioning nut
PIN PROFIBUS PA
1
PA+
2
not connected
3
PA–
4
shield, connected to ground
7ML19985XA82