SETTINGS
If you wish to change a parameter in this system menu, you will
be asked to enter a password (4-digit number).
NOTE! The password is set to "3197" in the factory. If the pass-
word is changed and then forgotten, the device must be re-ac-
tivated by the manufacturer' s customer service department. It
is not possible for the user to reset the system!
If more than about one minute passes in the system menu
without any entry being made, the control unit automatically
switches back to the standard display.

Level Control

2 Pressure switches
Digital system with two pressure switches and two air-pres-
sure sensors for
1. base load
2. peak load / high water alarm
2 Submersible switches
Single unit: Digital system with two submersible switches for
1. base load ON/OFF
2. peak load / high water alarm ON/OFF
3 Submersible switches
Single unit: Digital system with three submersible switches for
1. Base load OFF
2. base load ON
3. High water alarm ON/OFF
Duplex unit: Digital system with three submersible switches for
1. base load ON/OFF
2. High water alarm ON/OFF
3. Peak load ON/OFF
4 Submersible switches
Duplex unit: Digital system with four submersible switches for
1. pump(s) OFF
2. base load ON
3. High water alarm ON/OFF
4. peak load ON
Static pressure sensor
Analogue system with two air-pressure sensors for analogue
filling level detection and failure safety with a pressure switch
– Base load ON - OFF
In these menu items, the switch-on and switch-off points are
set for the base load pump. The value is defined in cm water
column, measured from the lower edge of the pressure bell.
NOTE! The switch-off level is fixed at 5 cm, measured from the
lower edge of the pressure bell.
• High water level
This menu item is used to define the water level in the collec-
tion chamber at which an alarm should be triggered. The value
is defined in cm water column, measured from the lower edge
of the pressure bell.
• Peak load ON - OFF
In these menu items, the switch-on and switch-off points are
set for the peak load pump. The value is defined in cm water
column, measured from the lower edge of the pressure bell.
• Upper edge of pump
The position of the upper edge of the pump, which is impor-
tant for the S2 time, is defined here. If the water level in the
chamber drops below this height, i.e. the motor is uncovered,
the runtime monitoring starts to monitor the running time of
the pump. The value is defined in cm water column, measured
from the lower edge of the pressure bell.
Analogue 4-20mA
Analogue system with 4 - 20mA submersible sensor (measur-
ing range 6m max.)
• Base load ON - OFF
In these menu items, the switch-on and switch-off points are
set for the base load pump. The value is defined in cm water
column, measured from the lower edge of the submersible
sensor.
NOTE! In order to prevent the measurement head from be-
coming soiled by solids in the sewage and possibly resulting
in measurement tolerances, never set the switch-off level for
submersible sensors to less than 4 cm.
• High water level
This menu item is used to define the water level in the collec-
tion chamber at which an alarm should be triggered. The value
is defined in cm water column, measured from the lower edge
of the submersible sensor.
• Peak load ON - OFF
In these menu items, the switch-on and switch-off points are
ENGLISH
21