INSTALLATION (CONTINUED)
Important:
Do not replace or lengthen the exhaust hose as this could cause the unit to malfunction.
NOT RECOMMENDED
WARNING: Any warranties included with this product will be voided if an extra extension hose is
added to the originally provided installation kit or if the installation is performed differently than the
manufacturer's instructions, without proper consultation. Please contact Customer Support for help
with installation procedures if needed.
The supplied exhaust hose has a diameter of 5.9" (15 cm) and can be extended from
12" to 47 " (30 cm to 120 cm).
Do not bend (to the extent shown below) the exhaust hose. A bent hose will block exhaust air and
cause the unit to malfunction or shut-off.
Make sure the back of the unit is at least 20" (50 cm) away from the wall. Do not place the unit in
front of curtains or drapes as this could obstruct the airflow.
Note: Due to the power input of the unit on start up, voltage drops may occur and this can influence
other equipment (e.g. dimming lights). Please make sure that the unit is connected to a supply with
a maximum permissible system impedance Zmax = 0.306 Ohm. If you require further clarification,
you may contact your local power supply authority.
RECOMMENDED
EN
6
20" (50 cm)