5.5.5 Examples
DS-8 not used
DS-7 not used
DS-6 not used
DS-5 AES
DS-4 Inverter voltage
DS-3 Inverter frequency
DS-2 Stand-alone mode
DS-1 Stand-alone mode
stand-alone
Example 1 (factory setting):
5 AES: off
4 Inverter voltage 230V
3 Inverter frequency 50Hz
To store the settings after the dipswitches are set according to the required values:
press the 'Up' button for 2 seconds (upper button to the right of the DIP switches, see
appendix A, position J). The overload and low-battery LED's will flash to indicate
acceptance of the settings.
The DIP switches can be left in the selected positions, so that the 'other settings' can
always be recovered.
off
DS-8
off
DS-7
off
DS-6
off
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
stand-alone
Example 2:
5 AES: off
4 240V
3 60Hz
off
DS-8
off
off
DS-7
off
off
DS-6
off
off
DS-5
off
off
DS-4
on
off
DS-3
off
off
DS-2
off
off
DS-1
off
stand-alone
Example 3:
5 AES: off
4 230V
3 60Hz
DS-8
off
DS-7
off
DS-6
off
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
stand-alone
Example 4:
5 AES: on
4 240V
3 50Hz
17