5. Installation

The tasks described in this section may only be
carried out by a qualified electrician.
5.1

Choice of location

The device is solely intended for fixed wall mounting. A
suitable location meets the following requirements:
„ Networked devices are in sufficient proximity to each
other (up to 300 m).
„ Technical data and mains data are the same.
Î "4. Technical data"
„ Permissible ambient conditions are observed.

5.2 Permitted ambient conditions

T
T
DANGER
Danger of injury and fire
If the device is operated in potentially explosive atmos-
pheres (explosive area), explosive substances may ignite
due to sparking of components of the device.
f Do not use the device in potentially-explosive atmos-
pheres (e.g. at gas filling stations).
T
T
ATTENTION
Device damage due to unsuitable ambient conditions
An unsuitable choice of location may cause damage to the
device. Please note the following points when choosing a
location:
f Check that the surface is suitable for wall mounting
(Wall structure with at least double-layer drywall).
f Do not place the device in areas at risk of flooding.
f Protect the device from direct water jet.
8
Permitted ambient conditions
Ambient temperature
Average temperature
over 24 hours
Altitude
Relative humidity

5.3 On-site installation

T
T
DANGER
Fire hazard due to device overload
There is a fire hazard due to overloading of the device
caused by unsuitable supply line.
f Route the supply line according to the technical data of
the device.
Supply line
f Route the supply line according to the technical data of
the device.
Î "4. Technical data"
When dimensioning the supply line (cross section
and line type), always ensure the following local
conditions:
„ Type of installation
„ Cable parameters per unit length
„ Line length
f Lay the supply line to the location. Possibilities for cable
entry can be found at the upper case (2 x M40) and at
the lower case (1 x M40 and 2 x M20) on the device.
For the cable entry from below, it is not possible
to loop through the supply line.
-25 ... +40 °C
< 35 °C
Max. 2,000 m above sea
level
max. 95 %
(non-condensing)