RME: Relay minimum enable time. Specifies the minimum amount of
time the relay should be enabled.
RDD: Relay disable delay. Specifies the amount of time the relay
disable condition must be present before acting upon it.
Al:
Alarm low voltage. When the battery voltage falls below this value
for more than 10 seconds the low voltage alarm is turned on.
Alc: Clear low voltage alarm. When the battery voltage rises above
this value, the alarm is turned off. This value needs to be greater
than or equal to Al.
Alarm high voltage. When the battery voltage rises above this
Ah:
value for more than 10 seconds the high voltage alarm is turned
on.
Ahc: Clear high voltage alarm. When the battery voltage falls below
this value, the alarm is turned off. This value needs to be less than
or equal to Ah.
AS: Alarm low SOC. When the state-of-charge falls below this value
for more than 10 seconds the low SOC alarm is turned on.
ASc: Clear low SOC alarm. When the state-of-charge rises above this
value, the alarm is turned off. This value needs to be greater than
or equal to AS.
A BUZ:
When set, the buzzer will sound on an alarm. After a button is
pressed the buzzer will stop sounding. When not enable the buzzer
will not sound on an alarm condition.
Rl:
Relay low voltage. When the battery voltage falls below this value
for more than 10 seconds the alarm relay will be activated.
Rlc: Clear relay low voltage. When the battery voltage rises above this
value, the relay will be de-activated. This value needs to be greater
than or equal to Rl.
Rh: Relay high voltage. When the battery voltage rises above this
value for more than 10 seconds the relay will be activated.
Rhc: Clear relay high voltage. When the battery voltage falls below this
value, the relay will be de-activated. This value needs to be less
than or equal to Rh.
SA: Maximum rated shunt current. If using a shunt other than the one
supplied with the BMV, set this to the rated current of the shunt.
SV:
The shunt output voltage at the maximum rated current. If
using a shunt other than the one supplied with the BMV, set this to
the rated voltage of the shunt.
BL I: Intensity backlight. The intensity of the backlight, ranging from 0
(always off) to 9 (maximum intensity).
12