The manufacturer will not be held liable for any underestimates made in the
structural consistency of the anchor prepared by the installer.
Therefore, pay utmost attention to the foregoing operation that could cause
serious injury/damage to people/property if carried out incorrectly.
When installing models equipped with heating pump, if no condensate discharge was built into the wall
(see paragraph 2.4.3), in order to drain the condensate it will be necessary to drill a hole through the
wall in the position shown on the template.
2.3.1.2 -

PREPARING THE CONDENSATE DISCHARGE

For machines equipped with heat pump, the condensation exhaust hose (supplied), to be inserted in the
specific coupling (A), must be connected to the air conditioner (fig. 1 - ref. N).
Remove the cap (6a) (fig. 7) before inserting the condensation drain pipe.
When the max level is reached, a solenoid valve ensures the condensate will flow out from the internal
tray.
For cold-only machines, connect the condensate discharge pipe if you intend running the unit at low
outdoor temperatures (lower than 23°C).
Since condensate drains by gravity, there must be a minimum slope of at least 3% at every point of the
discharge line. Use a rigid or flexible tube having an inside diameter of at least 16 mm.
If the line empties into a sewerage system, install a siphon before the point in which the pipe reaches
the main discharge, at least 300 mm below the inlet from the unit (fig. 8).
If the drainpipe drains into a vessel (tank or other container), this container should not be sealed and
the drainpipe should not remain immersed in the water (see fig. 10).
The hole through which the condensate pipe passes should always slope towards the outside (see fig.
5).
the exact position in which to place the pipe inlet, as compared to the machine, is shown on the drilling
template.
Make sure, in this case, that the water expelled outward does not damage or
disturb persons or property.
During the winter this type of drainage may cause sheets of ice to form.
When the condensate drainage is fitted, pay much attention not to compress
the rubber hose.
In the event of operation during the winter with temperatures equal to or lower than 0° C, make
sure that the condensate drain pipe is protected from freezing in order to ensure draining.
In the event of prolonged operation during the winter with temperatures below 5°C, install the
optional basin heater kit.
EN - 13