Mounting and Connection Instructions Siren Module
Select signaling device
Set the jumper
P4
Position H
Position N
ESSER signaling devices (160455.10 und 160456.10) may not be used in systems as per
VdS.
Attention:
When connecting the ESSER compact signaling
device 160455.10 and the audible alarm device
160456.10, the following monitoring resistors must be
changed in the signaling device:
Replace the resistors in the ESSER signaling devices
160455.10 and 160456.10:
R1 *
4k7
R2
12k1
R3 (2x)
12k1
* only 160455.10
The respective resistors can be found in the bag with
the accessories.
5.

Tear-off contact

5.1

Mounting in separate housing

Screw the spacer and the PCB with the tear-off contact to the mounting surface as shown.
Distance between the switch and the bottom plate approx. 2 mm or approx. 15 mm between the PCP
top and the bottom plate.
Place washer(s) underneath
Jumper P5
.
open
Washer above
Washer below for
adjustment
Bottom plate
Mounting surface
15 mm
2 mm
5.2

Mounting in the panel housing

Remove tear-off contact
(T
he tear-off contact of the Siren Module is not required, the tear-off contact of the control panel PCB
is used.
)
Close Jumper P5
.
compact alarm device Honeywell 048720.17
compact signaling device ESSER 160455.10
(instead of 10k)
(instead of 4k7)
(instead of 0 Ω)
to adjust positioning if necessary.
Sideview
height
ESSER 160455.10 and 160456.10
Flasch
electronics
Siren
generator
(included)
Jumper P5
open
with
closed:
without tear-off contact
(e.g. for installation in
Mounting
the panel housing)
surface
4k7 *
R1
* only 160455.10
12k1
R2
R3
Cover contact
12k1
:
tear-off contact
15
6
5
4
3
2
1