6.3
EXAMPLE OF CASCADE SYSTEM WITH DOMESTIC HOT WATER STORAGE CONNECTED TO THE
MASTER BOILER
1
HEATING FLOW PUMP
2
FLOW PROBE (QAD36)
3
RETURN PROBE (QAD36)
4
EXTERNAL SENSOR
Additional parameters to set apart from those described in sections 5.1 and 5.2:
Type of boiler
Menu
MASTER
Configuration
MASTER
Configuration
6.4
EXAMPLE OF CASCADE SYSTEM WITH INSTANTANEOUS DOMESTIC HOT WATER PRODUCTION
CONNECTED TO THE MASTER BOILER
1
ACS STORAGE BOILER FILLING PUMP
2
FLOW PROBE (QAD36)
3
RETURN PROBE (QAD36)
4
EXTERNAL SENSOR
Additional parameters to set apart from those described in sections 5.1 and 5.2:
Type of boiler
Menu
MASTER
Configuration
7105035.03 (1-10/11)
5
MASTER BOILER
6
ZONE VALVE
7
RADIATORS
8
AMBIENT THERMOSTAT
Parameter
Value to set
5731
Diverting valve
5736
ON
5
MASTER BOILER
6
ZONE VALVE
7
RADIATORS
8
AMBIENT THERMOSTAT
Parameter
Value to set
5736
ON
20
9
RELAY
10
ACS STORAGE BOILER PROBE
11
DOMESTIC HOT WATER STORAGE BOILER
n
BOILERS IN NON-MASTER CASCADE
Description
Configure element type for DHW circuit
Enable DHW circuit on single boiler
9
RELAY
10
ACS INSTANTANEOUS DRAW-OFF
n
BOILERS IN NON-MASTER CASCADE
Description
Enable DHW circuit on single boiler