28
Fault
Ursache
Does not switch
No power or power
too low (green LED
does not light up)
Electronic defective
Contacts welded
together (after short-
circuit)
Microwave barrier
defective
Switches
Incorrect setting of
incorrectly
change-over switch
for limit signal
Permanent alarm
Interrupt or short-cir-
signal
cuit line to microwave
barrier
Microwave barrier
defective
Maßnahme
Check power
Replace FTR 325
Replace FTR 325,
connect a fuse into
contactor circuit
Replace microwave
barrier and send it to
the manufactor for
reconditioning
Correctly set change-
over switch behind
front panel
Check line and con-
nections
Replace microwave
barrier and send it to
the manufactor for
reconditioning
Endress+Hauser