Measurement Data Registers
Accessing unavailable (temporarily missing) measurement data does not generate an exception.
"Unavailable" value (a quiet NaN) is returned instead.
Measurement output is shown in metric units. If non-metric values are needed in Modbus use, the
units shall be converted in the Modbus master (PLC) using the scaling functions typically available.
Table 4 Modbus Measurement Data Registers (Read-Only)
Register Number
Address
(Decimal)
(Hexadecimal)
1
0000
3
0002
9
0008
19
0012
27
001A
18
Register Description
Text string test
hex
Register Description
Relative humidity
hex
Temperature
hex
Dew/frost point
hex
temperature
Wet bulb temperature
hex
Enthalpy
hex
Data Format
Test Value
7-character
Text string
ASCII string
"-123.45"
Data Format
Unit
32-bit float
%RH
32-bit float
°C
32-bit float
°C
32-bit float
°C
32-bit float
kJ/kg
M211692EN-C