HUMIDITY TRANSMITTER HMD60U
HUMIDITY AND TEMPERATURE TRANSMITTER HMD60Y
MOUNTING
Figure 1 Dimensions of the HMD60U/Y
GROUNDING
Figure 2 Signal cable grounding with
bushing 18941HM
Downloaded from
www.Manualslib.com
62 (2.44)
250 (9.84)
Ø 12
(0.47)
100 (3.94)
Mounting hole 82 (3.23)>>>
manuals search engine
HMD60U/Y Operating Manual
The
HMD60U/Y
temperature transmitters are two-wire
transmitters. They are duct mounted, and
the electronics can be disconnected
without dismantling the installation.
Mount the transmitter with two screws.
Place the drilling template on the duct
surface and drill the holes as indicated.
Remember to drill an additional hole for
calibration purposes. The calibration can
be conveniently performed on site with
the HMI41 or HM70 portable indicators
equipped with an appropriate probe and
optional calibration cable.
Open the lid and mount the cable
bushing set 18941HM. Ground the cable
by connecting the contact tongues inside
the bushing to an exposed length of cable
braid as shown in Figure 2.
short-circuit risk, do not expose more
cable
braid
connecting the braid to the contact
tongues.