Emerson EXD-HP1 Betriebsanleitung Seite 4

Überhitzungsregler mit modbus kommunikation
Vorschau ausblenden Andere Handbücher für EXD-HP1:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Parameter description and choices
2Pd
Low pressure alarm cut-in (bar) circuit 2
2P4
Freeze protection alarm function
0 = disable,
1 = enable auto-reset,
2 = enable manual reset
2P2
Freeze alarm cut-out circuit2
2P5
Freeze protection alarm delay, sec.
2P-
Superheat control circuit2
(Kp factor), fixed PID
Display 1/10K
2i-
Superheat control circuit2 (Ti factor),
fixed PID
2d-
Superheat control circuit2 (Td factor),
fixed PID
Display 1/10K
2uH
High superheat alarm mode circuit 2
2uA
High superheat alarm setpoint (K) circuit 2
2ud
High superheat alarm delay (Min) circuit 2
C o n t r o l ( v a l v e ) s t a r t - u p b e h a v i o r :
(Parameter 1uu/2uu and 1u9/2u9)
1uu/2uu:
Min.:
10% (<1 sec.)
Default: 20% (< 1.5 sec.)
Max.:
100% (< 6 sec.)
E r r o r / A l a r m h a n d l i n g
Alarm
Description
code
Pressure sensor 1/2 error
1E0/2E0
Temperature sensor 1/2 error
1E1/2E0
Discharge hot gas
1Ed
temperature sensor 3 error
EXM/EXL electrical
1AΠ/2AΠ
connection error
Discharge hot gas
1Ad
temperature above limit
AF
Freeze protection
AF blinking
AL
Low superheat
(<0,5K)
AL blinking
AH
High superheat
AP
Low pressure
AP blinking
Failed
Err
uploading/downloading
Note: When multiple alarms occur, the highest priority alarm is displayed until being cleared, then the next highest alarm is displayed until all alarms are cleared. Only then will
parameters be shown again.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Operating instruction
EXD-HP1/2 Controller with ModBus
communication capability
Min
Max
0.5
18
0
2
-20
5
5
199
0.1
10
1
350
0.1
30
0
1
16
40
1
15
Related
Alarm
Valve
parameter
relay
-
Triggered
Fully close Check wiring connection and measure the signal 4 to 20 mA
-
Triggered
Fully close Check wiring connection and measure the resistance of sensor
-
Triggered
Operating Check wiring connection and measure the resistance of sensor
-
Triggered
-
Triggered
Operating
1P4/2P4: 1
Triggered
Fully close Check the system for cause of low pressure such as insufficient
1P4/2P4: 2
Triggered
Fully close
1uL/2uL: 1
Triggered
Fully close
1uL/2uL: 2
Triggered
Fully close
1uH/2uH: 1 Triggered
Operating Check the system
1P9/2P9: 1
Triggered
Operating Check the system for cause of low pressure such as refrigerant
1P9/2P9: 2
Triggered
Operating
-
-
-
www.emersonclimate.eu
U p l o a d / d o w n l o a d K e y : F u n c t i o n
Factory
• For serial production of systems/units, upload/download key allows the
setting
transmission of configured parameters among range of identical systems.
0.5
U p l o a d i n g p r o c e d u r e :
0
(storing configured parameters in key)
• Insert the key while the first (reference) controller is ON and press
the "uPL" message appears followed by "End" message for 5 seconds.
0
• Note: If the "Err" message is displayed for failed programming, repeat the above
30
procedure.
1.0
D o w n l o a d i n g p r o c e d u r e :
(configured parameters from key to other controllers)
• Turn off power to new controller
100
• Insert a loaded Key (with stored data from reference controller) into new controller
and turn on the power supply.
3.0
• The stored parameters of the key will be downloaded automatically into the new
controller memory; The "doL" message appears followed by a "End" message for
5 seconds.
0
• The new controller with new loaded parameters setting will start to operate after
30
"End" message disappears.
3
• Remove the key.
• Note: If the "Err" message is displayed for failed programming, repeat the above
procedure.
What to do?
Check wiring connection and measure the resistance of winding
Check valve opening/ check liquid flow for flash gas free/check
discharge hot gas temperature sensor
load on evaporator
Check wiring connection and operation of valve
loss
Repeat again the procedure for uploading/downloading
Date: 08.09.2017
Requires manual reset
after resolving alarm
No
No
No
No
No
No
Yes
No
Yes
No
No
Yes
No
EXD-HP12_OI_ML_R03_865921.docx
button;