G e n e r a l i n f o r ma t i o n :
EC3-X32 is the superheat controller with TCP/IP connection for stepper motor driven
EMERSON Electrical Control Valves EX4...EX8 and FX5...FX9.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure to comply can result in device
failure, system damage or personal injury.
• According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
• Do not exceed the specified maximum ratings for pressure, temperature,
voltage and current.
• Before installation or service disconnect all voltages from system and device.
• Do not operate system before all cable connections are completed.
• Entire electrical connections have to comply with local regulations.
Note: The EC3-X32 series contains
lead-acid battery.
The battery must NOT be disposed of with other commercial waste.
Instead, it is the user's responsibility to pass it to a designated collection point for the
safe recycling of batteries (harmonized directive 2012/19/EU). For further
information contact your local environmental recycling center.
M o u n t i n g p o s i t i o n :
The EC3-X32 is designed to be mounted onto a standard DIN rail. Mounting
position: on vertical walls, with stepper motor connector on top side only.
M o u n t i n g o f E C D - 0 0 2 :
• ECD-002 can be installed at any time also during operation.
• ECD-002 can be mounted in panels with 71x29
mm cutout.
• Push controller into panel cut-out.(1)
• Make sure that mounting lugs are flush with
outside of controller housing
• Insert Allen key into front panel holes and turn
clockwise. Mounting lugs will turn and gradually
move towards panel (2)
• Turn Allen key until mounting lug barely touches
panel. Then move other mounting lug to the same
position (3)
• Tighten both sides very carefully until keypad is
secured. Do not over tighten as mounting lugs
will break easily.
!
E l e c t r i c a l I n s t a l l a t i o n :
• Refer to the electrical wiring diagram for electrical connections.
• Do not apply voltage to the controller before completion of wiring.
• Ground the metal housing with a 6.3 mm spade connector.
• Keep controller and sensor wiring well separated from mains wiring. Minimum
recommended distance 30 mm.
• Use a class II category transformer for 24VAC power supply. Do not ground the
24VAC lines. We recommend using individual transformers for EC3 controller(s)
rd
and for 3
party controllers to avoid possible interference or grounding problems
in the power supply. Connecting any EC3 inputs to mains voltage will permanently
damage the EC3.
• The use of the relay is essential to protect the system in case of power failure if the
communications interface or the ECD-002 are not utilized.
• If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power
failure.
• In order to provide system protection in the event of power loss, it is recommended
to change the battery annually.
Digital input status is dependent to operation of compressor/thermostat
Commander
Operating condition
Compressor
Compressor starts
Compressor stops
Thermostat
Demand (compressor must be ON)
No demand
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
EC3-X32 Superheat Controller with TCP/IP
communication capability
a VRLA battery = valve regulated rechargeable
Digital input (I)
Closed / 24 V (Start)
Open / 0 V (Stop)
Closed / 24 V (Start)
Open / 0 V (Stop)
www.emersonclimate.eu
Operating instruction
W i r i n g :
A:
White wire
E:
M12 Plug cable assembly EXV-Mxx for connection to EX4...EX8 and
FX5...FX9.
G:
Remote control panel, system controller.
H:
Alarm relay, dry contact. Relay coil is not energized at alarm or power off.
I:
Digital input (0V/open = Stop; 24V/closed = Start)
J:
Transformer Class II, 24VAC secondary / 25VA
K:
Third party controller (can use the analog output signal from EC3)
O:
Pump down relay, dry contact. Relay is energized during normal operation.
Preparation for Start-up:
• Vacuum the entire refrigeration system.
• Note: EMERSON Electrical Control Valves EX4...EX8 and FX5...FX9 are
delivered at half open position. Do not charge system before closure of valve.
• Apply supply voltage 24V to EC3 while the digital input is 0V (open). The valve
will be driven to close position.
• After closure of valve, start to charge the system with refrigerant.
• Start the system and check the superheat and operating conditions.
Date: 03.04.2017
B: Black wire C: Blue wire D: Brown wire
EC3-X32_OI_ML_R13_865008.docx
loading

Inhaltszusammenfassung für Emerson EC3-X32

  • Seite 6 B e s c h r e i b u n g : V e r d r a h t u n g : EC3-X32 ist der Überhitzungsregler mit TCP/IP – Schnittstelle zur Steuerung der schrittmotorgesteuerten elektrischen Regelventile EX4…EX8 und FX5…FX9.
  • Seite 7 1 = ein mit Auto Reset 2 = ein mit Hand Reset PA Niederdruck-Alarm Ausschaltpunkt, barg -0,8 17,7 Niederdruck-Alarm Zeitverzögerung, sek. Niederdruck-Alarm Einschaltpunkt, barg -0,5 Emerson Climate Technologies GmbH www.emersonclimate.eu Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx...
  • Seite 8 *) Hinweis für R32: R32 ist in Europa als entflammbares Kältemittel eingestuft. EC3-X32 ist nach den Richtlinien für nicht brennbare Kältemittel entwickelt. Die Verwendung des EC3-X32 für R32 ist nur in Regionen zulässig in denen keine zusätzlichen Sicherheitsvorschriften für R32 bestehen bzw. Anzuwenden sind.
  • Seite 9 1- Sensor überprüfen eingestellte Sollwert Temperatursensoren 2- ECN-N60 Temperatursensor einsetzen 3- EMERSON Drucktransmitter verwenden: PT5-07x (für R22 / R134a / R507 / R404A / R407A / R407C / R407F / R124 / R448A /R449A / R450A / R513A / R1234ze) PT5-18x (für R410A/ R32)
  • Seite 10 > 35°C Batterielebensdauer < 2 Jahre Kennzeichnung A b m e s s u n g e n [ m m ] : EC3-X32 ECD-002 Emerson Climate Technologies GmbH www.emersonclimate.eu Am Borsigturm 31 I 13507 Berlin I Germany Date: 03.04.2017 EC3-X32_OI_ML_R13_865008.docx...