Preparations for Wiring
 Power Supply Wiring
• Be sure to use a dedicated line for power source.
• Be sure to earth this controller.
• Do not connect the earth wiring to those of gas pipe, water
pipe, lighting rod, telephone, etc.
 Type of wiring
• Use a fl exible wiring of 2 mm
• Use the standard power supply wiring for Europe (such as
H05RN-F or H07RN-F which conform to CENELEC (HAR)
rating specifi cations) or use the wiring based on IEC
standard (60245 IEC57, 60245 IEC66).
 Total Wire Length : 30 m or less
 Inter-Unit Control Wiring
 Type of wiring
• Use a fl exible shield wiring of 0.5 to 2 mm
• No polarity
 Total Wire Length : 1000 m or less
 Number of connectable units and devices :
(→ P.2 "Specifi cations")
Attention
• Ground the shield on both sides of shield wiring, otherwise an
operation error from noise may occur.
Wiring
Basic Wiring Diagram
N
L
Power source (100-240 V~ 50/60 Hz)
This unit
Power supply
wiring
L
N
Outdoor unit
U1 U2
+
Communication
Adaptor
U1 U2
Indoor unit
1. Turn the circuit breaker off before connecting the wiring
2. How to Attach the Ring Pressure Terminal
 For power supply wiring
Process the end of each wiring, and
attach the ring pressure terminal (fi eld
supplied item).
 For shield wiring
Process the end of the each wiring and attach the ring
pressure terminal (fi eld supplied item).
Remove wiring coat.
Cover with the tape.
Attach ring pressure
terminal.
3. Remove the
power switch
Power switch cover
cover
2
(Recommended).
.
2
Outdoor
unit
U1
+
U1 U2
U2
Inter-unit control
Communication
wiring
Adaptor
control wiring
• No polarity
• Polarity
present
U1 U2
U1 U2
Indoor unit
Indoor unit
1-1
1-2
Strip
Shield mesh
Strip
Insulation tape
Shield mesh
Ring pressure
terminal
Power-in port
Screw
 Communication Adaptor Control Wiring
(When connecting a Communication Adaptor)
 Polarity (+/-) present
 Number of connectable Communication Adaptor: up to 7 units
 For the type of wiring and total wiring length,
see "Installation Instructions" supplied with the
Communication Adaptor.
 External I/O Wiring
(When connecting external equipment)
 Type of wiring
• Use a fl exible wiring of 0.5 to 2 mm
 Wire Length : 20 m or less
Attention
• When using the controller at a location susceptible to noise,
use a shield wiring.
 LAN Cable
 Type of wiring
• Category 5 or above straight cable
 Wire Length : 100 m or less
Ground
4. Wiring
Connect the power supply wiring.
 Connect the power supply wiring and the earth wiring to
the power supply terminal board and the earth terminal
board
(on the sheet metal case) respectively.
*3
*3: Use earth terminal board as protective earth
• Do not over-tighten. (The screw may be damaged.)
Connect the inter-unit control wiring.
 Connect the shield part of the shield wiring to No. 0 (FG
of the signal terminal board (TB2).
*4: Functional Ground
• Do not over-tighten. (The screw may be damaged.)
 There is no polarity.
Connect the Communication Adaptor control wiring.

 Make sure the polarities (+/-) are correct.
Attention
• Read the "Installation Instructions" supplied with the
Communication Adaptor.
Connecting external equipment.

Attention
Ring
• See "Connecting to External Equipment" (P.5).
pressure
Fix the power supply wiring and other communication

terminal
wirings with the clamper (supplied) securely.
(Do not apply tensile force on the terminal connection part.)
Connect the LAN cable.

After all wiring arrangements are complete, turn
the circuit breaker on.
• Before power on, measure the voltage of the power supply
terminal board, and check it for the specifi ed voltage.
Turning the power on with a voltage other than the
specifi ed one may blow the fuse. If this occurs, no power
Screw
is supplied, and this unit may need to be replaced.
4
.
2
(When connecting to a network)
Ground
shield wiring
)