Drain Piping Work
• Drain pipe must be in downward gradient for smooth
drainage.
• Avoid installing the drain pipe in up and down slope to
prevent reversed water flow.
• During the drain pipe connection, be careful not to exert
extra force on the drain connector at indoor unit.
• The outside diameter of the drain connection at the flexible
drain hose is 20mm.
• Be sure to execute heat insulation (polyethylene foam with
thickness more than 8.0mm) on the drain piping to avoid
the condensed water dripping inside the room.
Drain Test
• Connect the main drain pipe to the flexible drain hose.
• Feed water from flexible drain hose to check the piping for
leakage.
• When the test is completed, connect the flexible drain hose
to the drain connector on the indoor unit.
Panel Installation
• The front panel can only be fitted in one direction, follow
the piping direction. (Observe the piping arrow sticker on
the front panel).
• Be sure to remove the installation template before installing
the front panel.
• Open the air intake grille by pulling back the catchers and
remove it together with the filter from panel.
• Install the front frame panel onto the indoor unit with 4
screws and tighten it completely to prevent cool air leakage.
• Connect the LED wire and air swing wire to the indoor
unit.
NOTE:
Install the front frame panel firmly to prevent cool air leakage which will cause condensation and water dripping.
Good Installation
Air Intake Grille Installation
• Before installed the air intake grille, make sure the air filter
is clip properly to the air intake grille.
• Install the air intake grille together with the air filter to the
front panel.
• The grille can be fit in any direction, when selecting
direction, the ceiling design and grille operability should
be considered.
• If the unit is come with ionizer filter (optional item), make
sure to fix the ionizer filter to the air filter before installed
the air intake grille.
• Fix the ionizer filter to the air filter with the black side on
top and white side at bottom.
• Carefully clip on the ionizer filter frame.
Indoor Unit
Cool Air
Ceiling Board
Panel
1-5
Indoor Unit
Pipe Clamp
Good
Feed Water
Flexible Drain Hose
NOTE:
This indoor unit uses a drain pump for condensed water
drainage. Install the unit horizontally to prevent water leakage
or condensation around the air outlet.
Open
LED Wire
From Front Panel
Air Swing
Wire
Cool Air
Air leak
Bad Installation
Bad
Main Drain Pipe
Screws
Control Box
Air leak
Ceiling Board
Panel
Frame
Ionizer
Filter