Accessory Part
• The indoor unit is provided with air discharge and air intake "knock-out" hole for duct connection. However the connection
of the short duct for air discharge is possible on only one side.
• The use of short duct for air discharge will improve airflow distribution if there is an obstruction (such as a lighting fixture)
or in a long, narrow room or an L-shaped room. It also use for air conditioning of two rooms simultaneously.
Possible Direction For Air Discharge And Air Intake
Air Discharge
Air Intake
Air Discharge
NOTE:
• Avoid using the short duct on which the air discharge grille can be completely closed, to prevent evaporator freezing.
• In order to prevent condensation forming, be sure that there is sufficient thermal insulation and no leakage of cool air when
installing the short duct.
• Keep the introduction of fresh air intake within 20% of total air flow. Also provide a chamber and use a booster fan.
Sealing Material
• It is possible to seal one of the four air discharge outlet. (sealing two or more air discharge outlet could cause a malfunction)
• Remove the front panel and insert the sealing material into the air discharge outlet on the indoor unit to seal the air outlet.
• The sealing material is the same length as the longer air discharge outlet. If it is desired to seal the shorter air discharge
outlet, cut the sealing material to shorten it.
• Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not touch the air louver.
Be sure not to push the sealing material in any farther than about 10mm.
CE Model
Preliminary Site Survey
Electrical supply and installation shall conform to the local
authority (e.g. National Electrical Board).
Voltage supply fluctuation must not exceed ±10% of the
rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high
supply fluctuation.
Ensure that the installation location is convenient for wiring
and piping.
Figure A
Please ensure that the following steps are taken:
Check the gradient for drainage flow as recommended in
Figure B.
Provide clearance for easy servicing and optimal air flow
as shown in Figure C.
The indoor unit must be installed such that there is no
short circuit of the cool discharge air with the warm
return air.
Do not install the indoor unit where there is direct
sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must
be a large distance away from the door.
Possible Opening Dimension For Duct Connection
Air Discharge
Air Discharge

Standard Mounting

Ensure that the overhead supports are strong enough to hold
the weight of the unit. Position the hanger rods (wall
mounting bracket for floor standing), and check for its
alignment with the unit as shown in Figure A. Also, check
that the hangers are secured and the base of the fan coil unit is
leveled in both horizontal directions, taking into account the
gradient for drainage flow as recommended in Figure B.
Model
Figure B
1-6
10
50
50
50
50
50
10
115
20
115
Air Discharge Knock Out Hole
20
25
A
1214
1214
B
666
666
C
273
273
D
130
130
E
1160
1160
F
27
27
G
77
77
H
745
745
I
25
25
J
209
209
K
486
486
L
108
108
M
360
360
PCD Ø140
Ø100
Air Intake Knock
Out Hole
30
40
50
1214
1714
1714
666
666
666
273
273
273
130
130
130
1160
1560
1560
27
27
27
77
77
77
745
1235
1235
25
25
25
209
331
331
486
486
486
108
108
108
360
600
600