Herunterladen Diese Seite drucken

ABB TZID-C Kurzanleitung Seite 2

Vorschau ausblenden Andere Handbücher für TZID-C:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Positioner TZID-C
Commissioning
1. Turn on the air supply to the positioner.
2. Apply the 4...20 mA analog input signal to the positioner
(terminals +11/-12).
3. Check for proper mounting:
-
Press and hold
MODE
-
Additionally briefly press
(manual adjustment within the sensor range)
is displayed.
-
Release
.
MODE
-
Press
or
to move the actuator to its mechanical
limit stops in both directions, and note the values. The
angle of rotation is indicated in degrees.
Recommended positions of limit stops:
> -28° and < +28° for linear actuators
> -57° and < +57° for rotary actuators
Minimum angle: 25°
4. Switch to the configuration level:
-
Press and hold
and
-
Additionally briefly press
-
Wait until the countdown from 3 to 0 is completed.
-
Release
and
.
The device will automatically go to parameter group P1._.
5. Select the actuator type (parameter P1.0); select ROTARY
or LINEAR using
or
This step must be performed prior to
Autoadjust ment (step 6).
6. Start the Autoadjust function:
-
Press and hold
MODE
-
Additionally briefly press
-
Release
.
MODE
-
Press
and keep it pressed until the count-
ENTER
down is finished.
-
Release
.
ENTER
Autoadjustment is started.
-
If the message "COMPLETE" is displayed to indicate
successful Autoadjustment, briefly press
acknowledge.
It is also possible that Autoadjustment is automatically
cancelled due to troubles, and an error message is dis-
played.
7. Adjust the tolerance band (only necessary for critical actu-
ators, e.g. especially small ones). Usually, this step is not
required.
8. If required, test the settings.
9. Save the settings:
-
Press and hold
MODE
-
In addition, briefly press
-
Release
.
MODE
-
Select NV_SAVE using
-
Press and hold
ENTER
completed, then release
The settings are saved in the non-volatile memory, and the
positioner returns to the operating level. The last previous
operating mode is activated again.
ABB Automation Products GmbH
Schillerstrasse 72 · D-32425 Minden
Phone: +49 (0) 57 18 30 - 0 · Fax: +49 (0) 57 18 30 - 18 60
http://www.abb.com
.
or
until mode 1.3
simultaneously.
.
ENTER
.
.
; until "P1.1" is indicated.
ENTER
.
until "P1.4" is indicated.
or
.
until the countdown is
.
ENTER
Quick Reference
Selecting the operating mode
Mode 1.0: Adaptive control
Press and hold
MODE
Additionally briefly press
°
C
%
mA
conf
Release
.
MODE
°
C
%
mA
is displayed, adaptive control is running.
conf
Mode 1.1: Fixed control
Press and hold
MODE
Additionally briefly press
°
C
%
mA
conf
Release
.
MODE
°
C
%
is displayed, fixed control is running.
mA
conf
Mode 1.2: Manual adjustment within the stroke range
Press and hold
MODE
Additionally briefly press
°
C
%
mA
conf
Release
.
MODE
°
C
%
is displayed.
mA
conf
to
Press
or
to adjust the position within the stroke range.
Mode 1.3: Manual adjustment within the sensor range
Press and hold
MODE
Additionally briefly press
°
C
%
mA
conf
Release
.
MODE
°
C
%
is displayed.
mA
conf
Press
or
to adjust the position within the sensor
range.
42/18-68 XA
.
as often as required.
is displayed.
.
as often as required.
is displayed.
.
as often as required.
is displayed.
.
as often as required.
is displayed.
Subject to change without notice.
Printed in the Fed. Rep. of Germany
42/18-68 XA Rev. 1.0
Issue 04.01

Werbung

loading