11 Troubleshooting

11.1

Messages (Ex and Px type codes)

Tab.39
Code
Description
Sensor error T5 (water temperature sensor)
Evaporator temperature sensor error T3.
Room temperature sensor error T4.
Compressor discharge TP temperature sensor error.
Compressor intake TH temperature sensor error.
Open circuit error on the immersion heater (IEH (dif­
ference in current between ON and OFF on the im­
mersion heater) < 1 A).
Protection against high discharge temperatures:
Tp > 115: Protection active.
Tp < 90: Protection inactive.
Protection against overloads on the compressor (ten
seconds after switching on the compressor, the cur­
rent overload control starts up).
1. If the compressor is running: if the current load is
> 7 A, the compressor is shut down and the pro­
tection activated.
2. If the compressor and the immersion heater are
running: if the current load is > IEH + 7, the com­
pressor is shut down and the protection activated.
Load value when the compressor and the electric
water heater start up at the same time: 14 A
(1550-W electric water heater).
7659610 - v02 - 08032017
If a malfunction occurs, the screen displays an error code beside the water
temperature indicator:
the "ALARM" pictogram appears,
the audible signal sounds.
1. Make a note of the code displayed.
The code is important for the correct and rapid diagnosis of the
type of error and for any technical assistance that may be needed.
2. Switch off and then switch the appliance back on.
The appliance starts up again autonomously when the reason for
the disruption has been cleared.
3. If the code is displayed again, correct the problem by following the
instructions in the table below:
11.1.1

List of messages

Check / Solution
Check the connection between the sensor and the
PCB.
Replace the sensor.
Check the connection between the sensor and the
PCB.
Replace the sensor.
Check the connection between the sensor and the
PCB.
Replace the sensor.
Check the connection between the TP sensor and
the PCB.
Replace the sensor.
Check the connection between the sensor and the
PCB.
Replace the sensor.
Check to ensure the immersion heater is not dam­
aged and that the cables have not been incorrectly
connected after a repair.
Check to ensure the compressor is not damaged and
that there are no refrigerant leaks.
Check that the TP and T5 sensors are not damaged.
Check to ensure the compressor is not damaged.
en
11 Troubleshooting
223