7.6. Switching the upper limit of cooling
temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool

DIP switch setting

Set the DIP switch SET 4 SW3 referring to the Table C.
ON
OFF
SW
1
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
ON
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.

7.7. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit ad-
dress settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number Default
number
00
Default
Filter indicator
11
01
Longer
interval
02
Shorter
00
Enable
01
Disable
Filter indicator
13
Display
action
only on
02
central
remote
controller
00
Default
Cool air
temperature
30
01
Adjust (1)
trigger
02
Adjust (2)
00
Default
01
Adjust (1)
Heat air
temperature
31
02
Adjust (2)
trigger
03
Adjust (3)
9374342273-01_IM.indb Sec1:18
9374342273-01_IM.indb Sec1:18
DIP switch "SET4"
SW
SW
SW
2
3
4
Cooling temperature setting range
Standard (18 to 30 °C)
Extension (18 to 32 °C)
Details
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the cool air trigger tempera-
ture. To lower the trigger tempera-
ture, use setting 01. To raise the
trigger temperature, use setting 02.
Adjust the heat air trigger tempera-
ture. To lower the trigger temperature
by 6 degrees C, use setting 01. To
lower the trigger temperature by 4
degrees C, use setting 02. To raise
the trigger temperature, use setting
03.
00
Enable
Auto restart
40
01
Disable
00
Super low
Cool Air
Follow the
43
Prevention
setting on
01
the remote
controller
00
Start/Stop
External
Emergency
46
01
control
stop
Forced
02
stop
00
All
Error report
Display only
47
target
on central
01
remote
controller
Follow the
Fan setting
setting on
00
when cooling
the remote
49
thermostat
controller
OFF
01
Stop

8. TEST RUN

8.1. Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.

8.2. Test run using Remote Controller

• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicators
fl ash slowly at the same time.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor unit
by this function in normal operation.
Be sure to operate by the control
unit, converter or external input
device.
Restrain the cold airfl ow with making
the airfl ow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
En-18