Herunterladen Inhalt Inhalt Diese Seite drucken

AirStage ARXD07GALH Installationsanleitung Seite 5

Innengeraet kanaltyp
Vorschau ausblenden Andere Handbücher für ARXD07GALH:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 22
3.3A.1. UNIT INSTALLATION EXAMPLE (CEILING
CONCEALED TYPE)
Connect the locally purchased duct.
(1) Inlet side
• Connect the duct to the locally purchased inlet fl ange.
• Connect the fl ange to the body with the locally purchased tapping screws.
• Wind the inlet fl ange connecting to the duct with the aluminum tape etc. to avoid the
air leakage.
When the duct is connected to inlet side, remove contained fi lter and surely attach
locally purchased fi lter at inlet opening.
(2) Outlet side
• Connect the duct with adjusting inside of outlet fl ange.
• Wind the outlet fl ange connecting to the duct with the aluminum tape etc. to avoid the
air leakage.
• Insulate the duct to avoid the dew condensation.
Check that duct work does not exceed the range of external static pressure of
equipment.
Make sure to insulate ducts to avoid the dew condensation.
Make sure to insulate between ducts and walls if metal ducts are used.
Please explain handling and washing methods of locally purchased materials to the
customer.
To prevent people from touching the parts inside the unit, be sure to install grilles on
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
When connecting the duct to the outlet port of the indoor unit, be sure to insulate the
outlet port and the installation screws to prevent water from leaking around the port.
AR07/09/12/14/18 Model
Set the static pressure outside the unit to 90 Pa or less (the allowable range is
between 0 and 90 Pa).
AR24 Model
Set the static pressure outside the unit to 50 Pa or less (the allowable range is
between 0 and 50 Pa).
Replace the cover as follows.
• Remove the screws, and then remove cover and fan guard.
• Install the cover with the screws as shown in the illustration below.
Model
AR07/09/12/14
AR18
AR24
9374342273-01_IM.indb Sec1:4
9374342273-01_IM.indb Sec1:4
CAUTION
CAUTION
Screw
9
11
13
screw
Cover
Fan guard
Side Inlet - Side Outlet
Insulation material (Field supply)
Aluminum tape
Flange (Field supply)
Air
Intake grille
Duct
(Field supply)
(Field supply)
Side Inlet - Side Outlet (Duct)
Insulation material (Field supply)
Aluminum tape
Flange (Field supply)
Air
Intake grille
Duct
(Field supply)
(Field supply)
Bottom Inlet - Side Outlet
Duct (Field supply)
Air
Intake grille (Field supply)
Air
Outlet side
A
Inlet side
B
109
AR07/09/12/14
A
650 mm
B
P200×2=400 mm
P200×3=600 mm
Air
Flange (Field supply)
Aluminum tape
Tapping screw for fl ange
connection (M4 x 10mm/
Field supply)
Air
25
P200
130
35
70
15
AR18
AR24
850 mm
1050 mm
P200×4=800 mm
En-4
7/12/2012 10:18:58 AM
7/12/2012 10:18:58 AM

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Arxd12galhArxd18galhArxd24galhArxd14galh

Inhaltsverzeichnis