Pressure Regulator - Emerson CPHE-Serie Betriebsanleitung

Heißgasbypass-regler

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Adjustment Table (FS= factory setting)
Evaporator
CPHE
Temp.
R134a R22 R407C R404A
°C
10
3,25
5
2
6,5
0
1
4,75
6,25
-10
-0,75
2,25
3,25
-20
FS
-30
Complaint
Regulator Leakage
Regulator hunting (chattering) – wide
fluctuation in controlled pressure
Regulator will not provide pressure
control
Regulator fails to close
Regulator is sized correctly but rated
capacity is not attained
CPHE_65008__R05
Operating Instructions

Pressure Regulator

CPHE and ACP
ACP
R134a R22 R407C R404A
R507
-
-
0,5
4,5
4
8
-
0,3
3
2,5
7,25
-1
1,8
1,3
4
-2,5
-0,75
FS
1,5
-1,8
-0,5
Possible Cause
Dirt in Regulator
Regulator oversized
Regulator and Evaporating Pressure Regulator have control
interaction
Regulator and Liquid Injection Valve have control
interaction
Regulator and cylinder unloaders have control interaction
Pressure adjusting stem is set at a point so high that suction
pressure never reaches the set point
External equalizer line upstream of evaporating pressure
regulator
Strainer clogged at the regulator inlet
MOPD exceeded across the solenoid or loss of supply
voltage
Solenoid coil burned out
seat damaged due to foreign material
Wrong type distributor for hot gas bypass to the evaporator
Dirt under seat of the regulator
Pressure adjusting stem is set at a point so high that suction
pressure never reaches set point
Blocked external equalizer
Improper line sizing
Replacement for 04
Emerson Climate Technologies GmbH
GB
Holzhauser Str. 180 - D-13509 Berlin
www.emersonclimate.eu
Suction Superheat Table for Liquid Injection Valve Charges (K)
Charge Code
R134a
CL
R507
GL
15 K
UL
30 K
5
3,5
1
-0,8
-2,3
Service Hints
Corrective Action
Clean Regulator
Refer to the selection table in Catalogue
Move external equalizer line downstream from the
Evaporating Pressure Regulator
Increase superheat setting. Dampen bulb response by
repositioning
Differential should be increased between the controls by
lowering the regulator's set point
Re-adjust the regulator acc. to operating instructions
Move external equalizer line downstream from evaporating
pressure regulator
Replace strainer
Replace solenoid or trouble-shoot the electrical problem
Determine cause and replace coil
Change valve or orifice
Install proper distributor for low pressure drop
Locate and remove dirt. Install strainer.
Re-adjust the regulator acc. operating instructions
Locate and remove stoppage
Increase line size or increase size of regulator
Date: 20.06.2013
Germany
R22
R407C
-
15 K
13 K
30 K
25 K
45 K
40 K
DWG Nr.: CPH EZ 005000/PCN 863003
R404A
R507
22 K
35 K

Werbung

loading

Diese Anleitung auch für:

Acp-serie