System configuration

System pattern X [ One remote controller ]
Lossnay unit
OA
EA
Power supply
OA: Outdoor air
SA: Supply air
EA: Exhaust air
RA: Return air
System pattern Y [ Two remote controllers ]
Lossnay unit
OA
EA
Power supply
Lossnay remote controller
(PZ-61DR-E)
System pattern Z [ Interlocked with City Multi indoor unit (M-NET connection) ]
City Multi indoor unit
OA
(Interlocking with Lossnay)
EA
MA remote controller
(If necessary)
1. Operation from remote controllers
ON/OFF
Operation mode
[Heating/Cooling/Fan]
Temp. setting
Fan speed
[FS1 / FS2 / FS3 / FS4]
Ventilation mode
[Heat recovery / Bypass / Auto]
Remarks
*1: When one of the two remote controllers is switched ON/OFF, the other remote controller switches ON/OFF synchronously.
*2: When one of the three remote controllers is switched ON/OFF, the other remote controllers switch ON/OFF synchronously.
Or when the indoor unit is switched ON/OFF, the system of the Lossnay unit and Dx-coil unit switches ON/OFF synchronously.
*3: Cannot be controlled by M-NET system controller nor MA remote controller of the indoor unit.
*4: Fan speeds can be changed by 0-10VDC input or a volt free contact and can be fixed at the fan speed 3 if necessary.
*5: The ventilation mode is set to the heat recovery mode during the heating and fan modes.
The ventilation mode can be set to the bypass ventilation mode by a volt-free contact if necessary.
Eng-4
RA
Dx-coil unit
SA
PZ-01RC
The dedicated remote controller for the Dx-coil
unit is described as "PZ-01RC" in this manual.
It is not an official model name.
RA
Dx-coil unit
SA
PZ-01RC
M-NET system controller
(If necessary)
Lossnay unit
Power supply
Lossnay remote controller
(PZ-61DR-E, if necessary)
System pattern X
From PZ-01RC
From PZ-01RC
From PZ-01RC
Fixed at FS4 *4
Fixed at automatic mode *5
-
Outdoor unit
Power supply
Outdoor unit
Power supply
RA
Outdoor unit
Dx-coil unit
SA
PZ-01RC
System pattern Y
From PZ-01RC or
PZ-61DR-E *1
From PZ-01RC
From PZ-01RC
Can be changed from
PZ-61DR-E.
Can be changed from
PZ-61DR-E.
-
Power supply
System pattern Z
From one of the remote controllers or when
the indoor unit is switched ON/OFF *2
Only from PZ-01RC *3
Only from PZ-01RC *3
Can be changed from PZ-61DR-E, M-NET
system controller or MA remote controller (for
the indoor unit). The selectable fan speeds
depend on the model of remote controller.
Can be changed from PZ-61DR-E or M-NET
system controller.
Dx-coil unit cannot be monitored nor operated
from M-NET system controller.