Test run (continued)
Step 5 Perform the test run and check the airflow temperature and auto vane.
Press the [F1] button to change the operation mode.
Cooling mode: Check that cool air blows from the unit.
Heating mode: Check that warm air blows from the unit.
Step 6 Confirm the operation of the outdoor unit fan.
The speed of the outdoor unit fan is controlled in order to control the performance of the unit. Depending on the ambient air, the fan will rotate at
a slow speed and will keep rotating at that speed unless the performance is insufficient. Therefore, the outdoor wind may cause the fan to stop
rotating or to rotate in the opposite direction, but this is not a problem.
Step 7 Stop the test run.
Press the [ON/OFF] button to stop the test run. (The Test run menu will appear.)
Trouble shooting
If an error code is displayed on the remote controller PZ-01RC, please follow the flow chart below.
No
"P1" error on PZ-01RC?
Yes
No
PZ-61DR-E is connected?
Yes
0206, 2600, 2601,
5109 or 0900 on PZ-61DR-E?
No
Refer to the service handbook
of Lossnay unit for details.
Test run
Pipe
Cool
Switch disp.
Mode
F1
F2
Refer to table 1
Yes
Refer to table 2
Remain
F3
F4
Eng-23