Remote controller (PZ-01RC)
(2) Function setting from remote controller PZ-01RC.
(Automatic recovery setting)
[Function No.01]
Please change this function to "Not available".
If automatic recovery needs to be used, set it from Lossnay unit. Refer
to the Lossnay installation manual for details.
Function No.
Setting data
1
01
2
(Factory setting)
The function setting below must be set as the factory setting.
If changed, please set to the factory setting.
No.
Factory setting data
02
1
03
1
04
2
05
2
06
2
07
3
15
1
16
1
17
1
21
1
24
2
28
2
Note
The factory setting of No.08, 09, 10, 11, 12, 13, 14, 18, 19, 20, 22, 23,
25, 26 and 27 are not set and the function is not available.
Check points
After installation work, please double-check the points below. If there is any trouble, it must be done correctly.
(1) Check points - Unit installation
Is the insulation wrapped around the outside ducts?
Is the outside ducts installed correctly?
Has the heat insulating work been completed for refrigerant and drain pipes?
Are refrigerant and drain pipes correctly routed?
Is the refrigerant R410A?
Has the gas leak test been conducted?
Has the drainage check been finished?
Have the valves at both the higher and the lower pressure sides been checked to be fully open?
Has power been supplied for 12 hours or more before test run?
(2) Check points - Wiring work
Is the power supply voltage correct?
Is the wiring work the same as wiring diagram?
Is the power supply cable connected to the terminal (TB6) certainly?
Is the ground cable connected to the screw certainly?
Are the cables properly secured using the cord clip and the PG connector?
Setting check
Contents
Not available
Available
[Refer to Installation method]
[Refer to Installation examples]
[Refer to Drain pipe work, Refrigerant pipe work] page 10
[Refer to Drain pipe work, Refrigerant pipe work] page 10
[Refer to Refrigerant pipe work]
[Refer to Refrigerant pipe work]
[Refer to Drain pipe work]
[Outdoor unit]
[Refer to Test run]
[Outdoor unit]
[Refer to Wiring diagram]
[Refer to Connecting the power supply cable]
[Refer to Connecting the power supply cable]
[Refer to Connecting the power supply cable]
page 9
page 7
page 11
page 11
page 10
page 22
page 16
page 14
page 14
page 14