Test run (continued)
<Table 1>
Code
P1
Lossnay unit failure or Dx-coil unit failure.
Liquid temperature thermistor (TH2) failure
P2
Freezing/ overheating protection
P6
Gas temperature thermistor (TH5) failure
P9
Communication failure between remote controller
E0 - E5
and PCB A
Communication failure between PCB A and outdoor
unit
E6 - E7
Fb
PCB A failure
Inlet air temperature thermistor (TH11) failure
PU
Remote controller is incompatible with this model.
"6831" or "Please wait"
remains displayed on
the remote controller for
more than 6 minutes.
<Table 2>
Error code on PZ-61DR-E or
M-NET system controller
0206
2600
2601
5109
0900
Others
-
-
Eng-24
Error
No. of flashing of
LED11 on PCB B
Model selection failure
1
5
PCB A failure
Communication failure between
PCB A and PCB B
6
Communication failure between
Lossnay PCB and PCB B
7
Water level is too high in the unit
2
Water sensor is not properly
3
connected.
Supply air thermistor failure
8
4
Drain pump test run
9
Lossnay failure
Drain pump maintenance sign
10
(2100 hours operation)
OFF
Normal operation
See table 2
• Check connection of thermistor.
• Check resistance value of thermistor.
0 ˚C; 15.0 kΩ
10 ˚C; 9.6 kΩ
20 ˚C; 6.3 kΩ
30 ˚C; 4.3 kΩ
• Check local system if air flow is reduced.
• Check outdoor fan motor.
• Check connection of thermistor.
• Check resistance value of thermistor.
For characteristics, refer to (P2) above.
• Check connection cable for damage or loose connections.
• Check system configuration of remote controller.
• Check that outdoor unit has not been turned off.
• Check connection cable for damage or loose connections.
• Refer to outdoor unit service manual.
• Replace PCB A.
• Check connection of thermistor.
• Check resistance value of thermistor.
For characteristics, refer to (P2) above.
• Use correct remote controller PZ-01RC (Number "BH00J360"
is displayed on the bottom.)
Error
• Check the model selection dip-switches (SW11-9 and
11-10 on PCB B), SW1-7 on PCB A and the actual
model name.
See table 1
• Check the lead wire cable is properly connected
between CN105 on PCB A and CN5 on PCB B.
• Check the PCB A is properly working.
• Check the connection cable (accesory) is properly
connected between CN20 on Lossnay PCB and
CN120 on PCB B.
• Check the power to Lossnay unit is properly supplied.
• Check the SW7-1 of Lossnay unit PCB is ON.
• Check the water level in the unit. If the drain pump is
broken the water level becomes high and then error
code 2600 will be displayed.
• Check the lead wire cable of the water sensor is
properly connected to CN10.
• Check the lead wire cable of the supply air thermistor
is properly connected to CN9.
• Check if SW11-1 on PCB B is OFF.
• Check Lossnay PCB and the service handbook.
• Check the drain pump if it works properly and replace
when necessary.
-