Electrical installation

Electrical installation
With this product, the wiring installation method will vary according to
the design of the system.
Perform electrical installation to meet local electrical regulations.
* Always use double insulated PVC cable for the transmission cables.
* Wiring work must be performed by qualified professionals.
* All supply circuits must be disconnected before obtaining access to
the terminal devices.

Names of components in control box

TB6
PCB A
SW4
SW3
SW2
SW6
SW1
1. Remove the black screws and the control box
cover

2. Connecting the power supply cable

Pass the power supply cable through the bush* and connect to the
TB6 terminal block using the round terminals. Connect the ground wire
to the screw and secure tightening the bush. (* Use an item that can
firmly secure the cable such as a PG connector.)
Insert the cutting
Screw for earth lead
TM1
Eng-14
PCB B
LED12
LED11
CN120
SW11
TM104
Ferrite
Black screws
Bush
PG connector
Power supply cable
D
L
B
C
A
N
S1
S2
S3
A Outdoor unit power supply
B Earth leakage breaker *1, *2
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Dx-coil unit/outdoor unit connecting cables
F Dx-coil unit
*1. If the installed earth leakage circuit breaker does not have a
function to protect over-current, install a breaker with that function
along the same power line.
*2. A breaker with at least 3.0 mm contact separation in each pole shall
be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active
phase conductors of the supply.
N
ote
In accordance with IEE regulations the circuit breaker/isolating switch located on
the outdoor unit should be installed with lockable devices (health and safety).
Dx-coil unit - Outdoor unit
Dx-coil unit - Outdoor unit earth
Dx-coil unit - Outdoor unit S1-S2
Dx-coil unit - Outdoor unit S2-S3
*3. Max. 45 m
*4. The values given in the table are not always measured against the
ground value.
Notes
1. Wiring size must comply with the applicable local and national code.
2. Dx-coil unit/outdoor unit connecting cords shall not be lighter than
polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Dx-coil unit power supply cords shall not be lighter than
polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
CAUTION
• Always separate the power supply cable and transmission
cable by 5 cm or more to prevent malfunctioning of the unit.
• If the length of the stripped Power supply cable is too long, the
conductors may touch and short out.
• Do not tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
F
TB6
S1
S2
S3
E
*3
4 × 0.75 (polar)
*3
*4
230 V AC
*4
24 V DC