INsTALLATIoN
Settings
„P15 : Humidity protection interval
If you set fan stage 0, the appliance switches to a 24 hour dormant
phase. The humidity protection control unit only starts after this.
The appliance measures the humidity of the extract air for the
time set in P16. The appliance compares the last measured value
with the limit value set in P17. If the limit value is exceeded, the
appliance starts to ventilate. The appliance stops the ventilation
once the limit value is fallen below. At this point, the humidity
protection interval restarts, at the end of which the moisture is
measured.
„P16 : Start-up time for humidity measurement
The appliance measures the humidity of the extract air for the time
set in P16. The appliance compares the last measured value with
the limit value set in P17.
„P22 : Enable preheater
Effect
0 The internal preheater is completely deactivated.
1 The internal preheater is activated. In order to keep the heat exchanger
free from ice, the preheater ensures a minimum supply air temperature
with reference to the frost protection temperature adjustable in parameter
P18.
While this parameter is being displayed or adjusted, the "frost
protection" symbol is shown on the display.
„P24 : Passive cooling release temperature
To enable checking of the other parameters for passive cooling,
the outdoor air temperature must be no less than the value set
in this parameter.
„P25 : Passive cooling blocking temperature
If the outdoor air temperature falls below this blocking tempera-
ture, passive cooling is deactivated.
„P26 : Passive cooling hysteresis
To make cooling possible, the outdoor air temperature must be
lower than the extract air temperature by the value set in this
parameter.
„P27 : Temperature differential for enabling passive
cooling
Use this parameter to define the temperature differential that must
be exceeded for passive cooling to be
cooling to be enabled, the following condition must be met.
P3 = 2 : Outdoor air temperature > set room temperature + P27
P3 = 3 : Extract air temperature > set room temperature + P27
„P29 : Appliance type
This parameter is set at the factory. The parameter can only be set
after the controller assembly has been replaced.
www.stiebel-eltron.com 
enabled.
In order for passive
„P30 : Temperature for enabling frost protection
The unit only activates frost protection heating if the outdoor air
temperature drops to the value that can be set in this parameter.
„P31 : Enabling of humidity-dependent flow rate
control
With humidity-dependent flow rate control, the air flow rate is
increased or decreased depending on the humidity level.
„P70 : Delete fault list
To delete the fault list, set this parameter to 1. Press the "OK"
button to confirm. Afterwards, 0 is displayed again and the fault
list is deleted.

12.2 Actual values

Description
I1
Passive cooling status
I2
Extract air temperature
I3
Relative humidity of extract air
I4
Filter service life
I5
Appliance software version
I6
Unit software patch
I7
Terminal device serial number
I8
Programming unit software version
I9
Outdoor air temperature
I10
Supply air temperature
I11
Exhaust air temperature
I12
Relative humidity of outdoor air
I13
Extract air dew point
I15
Supply air fan drive output
I17
Exhaust air fan drive output
I19
Percentage output of internal preheating
I20
Ventilation unit operating time
I21
Fan operating time
I23
Fan speed, supply air fan
I24
Fan speed, exhaust air fan
I70-79 Fault
12.3 Code
„Cod
Enter 1000 to enable actual values and parameters, which are
reserved for qualified contractors. "A1" is shown on the display
when this is entered correctly.
Unit
°C
%
h
°C
°C
°C
%
°C
%
%
%
d
d
rpm
rpm
LWZ 130  |
45