Important:
• If an array of several devices is installed, a valve assembly must be fi tted to each tank and
a non-return fl ap on the overall supply pipe.
• If the pressure of the distribution network exceeds 5 bar, a pressure reducer must be fi tted
to the overall supply pipe.
• For operation with a hot water output temperature above 60°C, ensure the installation
EN
complies with the regulations in force. A thermostatic mixer valve may be necessary to
obtain an acceptable temperature at the tap (50°C).
• If metal piping is used, use a cast-iron sleeve or a dielectric pipe joint (brass connectors
are prohibited).
5.3. Hydraulic safety installation
5.3.1. Safety units:
Safety units are always installed on the cold water inlet to the tank. When installing the unit,
respect the fl ow direction indicated by arrows on the body of the security unit.
5.2.1. Safety valves:
The safety valves are fi tted to the tank inlet using a T (see diagram below).
1 single G 1¨ unit
No non-return valve or fl ap should ever be fi tted between the safety valve or safety unit
!
and the water heater.
A non-return fl ap preceded by a valve must be fi tted to the cold water inlet if the water heater
is equipped with a safety valve. To avoid scaling of these components, operate the safety
unit at least once a month by moving its controls to various positions.
Page 20 / 90
SAFETY UNIT
On cold water inlet only
1¼¨ kit with 2 G 1¨ units

SAFETY VALVE

On tank inlet
Valve diameter ≥
tank connector diameter
Safety valve/non-return fl ap/valve
U0594062-#