Herunterladen Inhalt Inhalt Diese Seite drucken

Specifications; Standard Cable Socket (Only Ns 100 And 160); Cable Outlet (Only Ns 50 And 63); Inductive Contact Model 831 - WIKA PGS23 Betriebsanleitung

Manometer mit induktivkontakt, für explosionsgefährdete bereiche
Vorschau ausblenden Andere Handbücher für PGS23:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

9. Specifications

9. Specifications
DANGER!
Danger to life due to loss of explosion protection
The non-observance of the instructions for use in hazardous areas can lead to
the loss of the explosion protection.
Adhere to the following limit values and instructions.
The case contains parts made of non-metallic material, which could be
adversely affected by environmental conditions. It must be ensured that the
non-metallic parts are not damaged as a result of the environmental condi-
tions.
Non-metallic parts of the case
PUR, TPU, PA 6, EPDM, NBR (option), FMQ (option)

9.1 Standard cable socket (only NS 100 and 160)

Cable socket, fitted on the right-hand side of the case.
Material: PA 6, black
Per VDE 0110 insulation group C/250 V
Cable gland M20 x 1.5 (facing downwards) with strain relief
6 screw terminals + PE for conductor cross-section 1.5 mm²

9.2 Cable outlet (only NS 50 and 63)

Cable length 2 m, facing downwards and to the right
Material: PVC

9.3 Inductive contact model 831

The recommended setting range of the contacts is 10 ... 90 % of the scale (0 ... 100 % on
request).
Contact version (see product label)
831, for NS 63 only
831-N
831-SN, safety version
831-3.5N
831-3.5SN, safety version
831-3.5S1N, safety version
1) only operate with corresponding isolating amplifier (see chapter 9.4, model 904.3x)
Pressure gauges with inductive contact model 831, for hazardous areas
1)
1)
, inverted signal
1)
EN
23

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Pgs43Dpgs43532.54Typ 831

Inhaltsverzeichnis