5. Commissioning, operation
The measuring line should be designed and installed so that the loads occurring due to
expansion, vibration and thermal effects can be absorbed. With gaseous media, a drain
should be provided at the lowest point; with liquid media, a vent should be provided at the
highest point.
The measuring instruments must be mounted in the common mounting position per EN
837-1, with a max. permissible incline of 5° on all sides.
Measuring assemblies
Proven measuring assemblies for various types of media.
Liquid media
Filling of the
liquid
measuring
line
Examples
conden-
sate
Pressure
gauge above
the tapping
point
Pressure
gauge below
the tapping
point

5.2 Electrical connection

The electrical connection must only be made by qualified skilled personnel. The instrument
must be connected to the equipotential bonding of the plant.
→ For performance data see chapter 9 „Specifications"
Supply voltage non-Ex version
Suitable supply voltage
Model KFA6-STR-1.24.500, AC 115/230 V, for DIN rail, order number: 7305636
Supply voltage Ex version
The instrument must only be used in conjunction with a corresponding Ex repeater power
supply.
Suitable Ex repeater power supply
Model KFD2-STC4-Ex1, DC 20 ... 35 V, for DIN rail, order number: 2341268
Pressure gauges with output signal, optionally for hazardous areas
liquid with
completely
vapour
vapourised
boiling liquids
"liquid
gases"
Gaseous media
gaseous
partially
condensed
(damp)
dry air
moist air
flue gases
EN
completely
condensed
steam
17