ALD measures the atmospheric pressure within a range of 850 - 1150 mbar and converts it into a standard signal of 0 -10 V or
4...20 mA respectively. The sensor system is designed for measurements in clean air and other non-aggressive, non-condensing gaseous media. Areas
of application for this pressure sensor include ventilation and air conditioning technology, air-pressure-dependent control systems, meteorological
measurement stations and climate observation units. The pressure sensor excels thanks to its high accuracy, long-term stability and reliability. A
variant with an additional display for pressure reading is available.
TECHNICAL DATA
Power supply:
Output signal:
Current consumption:
Electrical connection:
Medium:
Type of pressure:
Measuring range:
Max. pressure:
Accuracy:
Long-term stability:
Linearity:
Temperature drift values:
Hysteresis:
Ambient temperature:
Operating range:
Storage temperature:
Turn-on time:
t90 :
Enclosure:
Enclosure dimensions:
Cable gland:
Electrical connection:
Humidity:
Protection class:
Protection type:
Standards:
Features:
PREMASGARD
®
ALD – Measuring transducers for atmospheric pressure
Type ⁄ WG01
ALD - I
A L D - I
A L D - I - D I S P L AY
ALD - U
A L D - U
A L D - U _ D I S P L AY
Conversion table for pressure values:
Unit
=
1 Pa
1 kPa
1 bar
1 mbar
1 mH
O
0.0980665 bar
2
ALD
5 ... 36 V DC for I variant
24 V AC (half-wave rectification) for U variant
0 - 10 V or 4...20 mA
max. 20 mA (at 24 V DC)
2- or 3-wire connection
clean air and other non-aggressive, non-combustible gases
atmospheric pressure ⁄ absolute pressure
850 - 1150 mbar ⁄ 750 - 1250 mbar (selectable via DIP switches)
2000 mbar
± 1.5 % of final value at +20°C
± 0.5 % of final value per year
± 0.5 % of final value
± 0.5 % of final value per 10 K
± 0.1 % of final value
– 10...+ 50 °C
10 ... 95 % r.H.
–20...+ 50 °C
< 1 min
0 s ⁄ 1 s ⁄ 5 s ⁄ 10 s (selectable via DIP switches)
plastic, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), enclosure cover for display is transparent!
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
M 16 x 1.5; including strain relief, exchangeable, max. inner diameter 10.4 mm
0.14 - 1.5 mm², via terminal screws
< 95 % r.H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
illuminated single line display, cutout 36 x 15 mm (W x H)
indicating atmospheric pressure ⁄ absolute pressure
Measuring Range (adjustable)
850 - 1150 mbar ⁄ 750 - 1250 mbar
850 - 1150 mbar ⁄ 750 - 1250 mbar
850 - 1150 mbar ⁄ 750 - 1250 mbar
850 - 1150 mbar ⁄ 750 - 1250 mbar
bar
0.00001 bar
0.01 mbar
0.01 bar
10 mbar
1 bar
1000 mbar
0.001 bar
98.0665 mbar
Output
4...20 mA
4...20 mA
0 - 10 V
0 - 10 V
mbar
Pa
1 Pa
1000 Pa
100000 Pa
1 mbar
100 Pa
9806.65 Pa
Rev. 2017 - V11 GB
Display
Item No.
I - variant
1301-1152- 0080- 100
■
1301-1152-1080- 100
U - variant
1301-1151- 0080- 100
■
1301-1151- 1080-100
kPa
0.001 kPa
0.000101971 mH
1 kPa
0.101971 mH
100 kPa
10.1971 mH
0.1 kPa
0.0101971 mH
9.80665 kPa
mH
O
2
O
2
O
2
O
2
O
2
1 mH
O