  • DEUTSCH, seite 1
Note: The control unit is maintenance-free
6.1

Setting the maintenance date

The maintenance date is set using menu 2, Item 2.3. Follow the dialogue on the screen (see also3.5, Settings,
menu).
6.2

Troubleshooting

Display text
Battery error
Maintenance date (flashing)
Undercurrent 1 and/or 2
Overcurrent 1 and/or 2
Relay error 1 and/or 2
Power outage
Temp. error 1a and/or 2a
Temp. error 1b and/or 2b
Level error
Phase loss
Rotation error
Motor protect 1 and/or 2
Pressure loss
Rel. actv totl 1 and/or 2
Max. run time 1 and/or 2
Max. run occur 1 and/or 2

6 Maintenance

Possible cause
Battery is missing, is faulty or voltage is less
than 13.5 V
- Maintenance date has been reached - No
maintenance date entered
- Minimum power usage of the pump has not
been reached - Cable from the control unit to
the pump is
interrupted - Pump faulty
Maximum power usage of the pump has been
exceeded, possible blockage of the blade
wheel
Power contactor does not switch off
- Power supply has failed - Unit fuse has failed
- Main switch is faulty - Mains supply cable is
interrupted
Coil temperature switch has triggered
Coil temperature fuse has triggered
Incorrect arrangement and/or cabling of the
sensors (float switches, pressure switches,
level sensor or integrity of the pressure system)
Phase L1, L2 or L3 not available
Incorrect rotation in the power connection
- Motor protect switch has triggered - Motor
protect switch is set incorrectly
- Pump current is too high due to faulty or
blocked pump - Excessive current due to
phase loss
The hose at the screwed connection to the
immersion pipe (or plunger) and/or control unit
is leaking
Total run occur exceeded
Pump runs for too long per pump procedure
Pump runs too frequently in a short period of
time
Remedial action
Check battery connection and replace battery, if
necessary
- Carry out maintenance - Enter maintenance
date (see 6.1)
Check cable and replace, if necessary; check
pump and replace, if necessary
Clean the pump and check the blade wheel for
smooth running; replace, if necessary
Disconnect control unit from the mains and
replace contactor
- None; general power outage - Check fuse
- Check main switch - Check mains supply cable
When switching off deliberately, shut the control
unit down (see 4.4)
Resets itself as motor cools down. After a
successful attempt to switch back on, the error
message acknowledges itself. If a temperature
error persists, replace the pump
No self-reset as the motor cools down. Error
message cannot be acknowledged; replace
pump
Function check, troubleshooting
Check connection of the power cable and fuses
Exchange 2 phases of the supply cable
- Set the current value according to the pump -
Remove blockage
- Replace pump, if faulty - Check mains for phase
loss
Check the integrity of the pressure sensor
system
Can be acknowledged. Inform Customer Service
Error appears after 1,000 more run occurs
Check station arrangement and inform Customer
Service, if necessary
Check station arrangement and inform Customer
Service, if necessary