5 MESSAGGES AND ALARMS

Messagges
Model
Active (leakage)
MMW
MMA
High Temperature
MMW
MMA
Minim.Threshold
MMW
MMA
No Water
MMW
MMA
PrsSensor Fault.
MMW
MMA
Overpressure
MMW
Alarm
Description
Type
Hydraulic
Possible leakages in the hydraulic system (par.60).
Hydraulic
MMW: The water temperature has exceeded the
limit of 75° C - automatic restart when the
temperature drops below 60 ° C.
MMA: The heatsink temperature has exceeded the
limit of 75° C (thermal protection). Automatic reset
when the temperature drops below 50°C.
The external cooling fan starts when the
temperature reaches 50 ° C.
Hydraulic
Pump not primed.
Lack of water in the suction side.
Pump with poor performance.
Water demand is too high.
Broken pipe on the discharge side.
Incorrect parameters 22, 41
Hydraulic
Pump not primed
Lack of water on the suction side.
Incorrect parameters:
MMW: par. 22, 39, 43.
MMA: par. 22, 78, 43.
Hydraulic
Pressure transmitter is in fault
Electric
Hydraulic
Valves on the putput side have been closed too fast
and the pressure exceeds the double of the set
point.
Action Type
Eliminate leakages of the system to reduce running time of
the pump and extended pump starts.
Check that the water temperature is within specifications of
the product.
Check that the ambient temperature is within specifications
of the product.
MMA: Check air flow for cooling of the drive
Check and restore the proper priming of the pump.
Check presence of water on suction side.
Restore the proper priming of the pump.
Make sure the filter is not clogged.
Check for cracks in the hydraulic system pipes.
Check the correct pump selection for the type of plant.
Check the setting of the parameters 22, 41.
For reset, remove power, wait until the display goes off and
restore power.
Check presence of water in suction side.
Restore the proper priming of the pump.
Make sure the filter is not clogged.
Check the setting of the mentioned parameters:
For reset, remove power, wait until the display goes off and
restore power.
MMA: check the sensor and sensor cable wiring.
MMA/MMW: check the sensor reading using the pressure
gauge, if installed.
When not functioning properly, replace the sensor.
Install appropriate compensating hydraulic shock
absorbers.
If not installed, install the expansion vessel.
If present, check the air pressure side of the vessel.
en
57