4 PROGRAMMING

AQUONTROLLER has three menu levels:
RAPID INSTALLATION MENU
You can view and edit the basic parameters of operation for quick and easy programming, such as:
language, motor nominal current, pressure. Detailed descriptions see section 5.1.
MAINTENANCE MENU
You can view and modify various functions in the rapid setup menu as additional parameters for quick and
complete calibration system. Detailed descriptions see section 5.2.
EXTENDED MENU (access with password)
You can view and edit all the operating parameters, including the rapid setup menu and maintenance
menu. It is necessary to access this menu, mainly in case of problems stopping the inverter and / or
oscillation.
Detailed descriptions see section 5.3.
Key functions:
KEYS PRESSED
+
+
+ ENTER
-
-
- ENTER
ENTER (for 2 seconds)
ENTER
+ -
From the main menu:
+ (for 5 seconds)
ENTER
- (for 3 seconds)
+ - ENTER (all together)
Or
ENTER (all together)
To Start/Stop (ON/OFF) the pump, press the "–"button for 3 seconds!
EFFECT
Increase
Fast increase
Very fast increase
Decrease
Fast decrease
Very fast decrease
Save (only possible when password has been entered)
Show next parameter
Show previous parameter
Fast exit from the maintenance menu or extended menu
Go to maintenance menu (from main menu)
Current and power abosorbed by pump are shown in the display
Pump ON / OFF
Go to extended menu (from main menu)
en